| Date |
Text |
| 2019-06-06 14:55:19 | 2ND REVIEW: 19020657 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT A103 THE ALCOVE FOR THE LAVATORY IN THE THE |
| | PATIENT TOILET IS TO SMALL FOR THE REQUIRED 30"X 48" |
| | CLEAR FLOOR SPACE THE ALCOVE SHALL BE A MIN OF 30" PER |
| | FBC ACC 606.2. 305, 306 |
| | |
| | 2. SHOW THE CLEAR FLOOR FOR THE LAVATORY , TOILET AND |
| | THE TURNING SPACE. PER FBC ACC 603.2.1, 606.2 |
| | |
| | 3. SHT. P901 SHOW THE REQUIRED SHUT OFF VALVES ON ALL |
| | THE DROPS. PER FBC PL 606.1(5) |
| | |
| | 4. THE NEW HOT WATER SHALL COMPLY WITH FBC PL 607.2 HOT |
| | OR TEMPERED WATER SUPPLY TO FIXTURES.THE DEVELOPED |
| | LENGTH OF HOT OR TEMPERED WATER PIPING, FROM THE SOURCE |
| | OF HOT WATER TO THE FIXTURES THAT REQUIRE HOT OR |
| | TEMPERED WATER, SHALL NOT EXCEED 50 FEET . |
| | RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING |
| | SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED |
| | WATER. |
| | |
| | 5. THE NEW HOT WATER PIPING SHALL BE INSULATED PER FBC |
| | PL E] 607.5 |
| | |
| | 6. A MIN OF 1 SINK IN THE EXAM ROOMS SHALL COMPLY FBC |
| | ACC 212.3, 606.2, 606.3 |
| | |
| | . |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |