Plan Review Notes
Plan Review Notes For Permit 19020657
Permit Number 19020657
Review Stop M
Sequence Number 1
Notes
Date Text
2019-03-12 17:34:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020657
 3/12/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M101 & M102: REFER TO TABLE 7-1 ASHRAE 170-2008 AND
 PROVIDE A DESIGN PARAMETERS (PRESSURE RELATIONSHIPS
 ETC.) SCHEDULE FOR THE ROOMS AND SPACES IN THE WORK
 AREAS. I AM NOT SEEING A "PHARMACY" ON THE PLANS. IS
 THIS A GENERAL TERM FOR THE WORK AREA OR DOES IT REFER
 TO A SPECIFIC ROOM OR SPACE? - SECTION 107.2.1 WPB.
  
 2) SHEETS A102 & M102: THE LOCATIONS OF THE HAZARDOUS
 IV PREP AND NON-HAZARDOUS PREP IV ON THE MECHANICAL
 PLAN DO NOT MATCH THE LOCATIONS ON THE ARCHITECTURAL
 PLAN- SECTION 107.2.1 WPB.
  
 3) M102, NOTE #3: THE HAZARDOUS EXHAUST DUCT FROM THE
 LAB HOOD SHALL BE INDEPENDENT OF THE OTHER EXHAUST
 SYSTEMS- SECTION 510.4 FBC M. A) THE HAZARDOUS EXHAUST
 DUCT SHALL EXTEND DIRECTLY TO THE EXTERIOR OF THE
 BUILDING AND SHALL NOT EXTEND INTO OR THROUGH DUCTS AND
 PLENUMS- SECTION 510.6.7 FBC M. B) REFER TO SECTION
 510.9 AND INDICATE THE TYPE OF LAB HOOD EXHAUST DUCT
  
 TO BE INSTALLED. C) PROVIDE AN EQUIPMENT SCHEDULE FOR
 THE LAB HOOD AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 WITH A SPEC SHEET STAMPED BY THE ENGINEER OF RECORD-
 SECTION 304.1 FBC M.
  
 4) REFER TO SECTION 414.1.3 FBC B: PROVIDE A HAZARDOUS
 MATERIALS REPORT THAT INCLUDES MATERIAL QUANTITIES, AND
 SUBMIT MSDS SHEETS FOR ALL MATERIALS TO BE STORED OR
 PROCESSED IN THE HAZARDOUS IV PREP ROOM AND ALL OTHER
 ROOMS AND SPACES.
  
 5) M102: WHAT IS THE PURPOSE OF THE EXHAUST SYSTEM IN
 THE UNPACK ROOM- SEE TABLE 7-1 ASHRAE 170-2008 AND
 INCLUDE THE ROOM IN THE DESIGN PARAMETERS SCHEDULE.
  
 6) M102: THE PLAN APPEARS TO SHOW THE RETURN DUCTS IN
 THE HAZADOUS AND NON-HAZARDOUS ROOMS CONNECTING INTO
 THE SUPPLY DUCT TO THE FFU'S- PLEASE CLARIFY
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  