2019-02-25 09:05:27PERMIT # 19020657
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) COVER SHEET: UPDATE THE CODE LIST TO REFERENCE THE
 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 2) PERMIT WAS ENTERED AS SUITE #100, HOWEVER PLANS
 INDICATE THAT THE WORK IS ON THE 14TH FLOOR. PLEASE
 REVIEW AND CORRECT WHERE NEEDED.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE