Plan Review Notes
Plan Review Notes For Permit 19020657
Permit Number 19020657
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-11 14:08:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020657
 ADD: 525 OKEECHOBEE BLVD. 14TH FLOOR / ADDITIONAL EXAM
 ROOMS & PHARMACY
 CONT: TBD/ TO BE DETERMINED
 TEL: ?????????????
 E-MAIL: [email protected] CONTACT: JIM
 PITZER
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 11/ 2017
 ACTION: DENIED
  
 1) THE 16 SHEETS SUBMITTED UNDER THE REGISTERED
 ARCHITECT ROBERT L. BOSTWICK ARE NOT ELECTRONICALLY
 SIGNED NOR SEALED.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 2A) SHEET 002_FL110- LIFE SAFETY PLAN LIST THE CODE
 REFERENCES BUT THE CODE SUMMARY STATES THIS IS A
 RENOVATION, BUT DOES NOT REFERENCE THE 2017 FLORIDA
 BUILDING CODE EXISTING BUILDING CODE. THE FAMILY OF THE
 2017 FBC WAS ADOPTED ON DEC. 31/ 2017.
  
 2B) THE PLANS ARE SILENT AS TO WHICH METHODOLOGY UNDER
 THE 2017 EXISTING BUILDING CODE THE PLANS WERE
 DEVELOPED?
 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 3) SHEET 011_A101 DETAIL 18 SHOWS WHAT APPEARS TO BE
 (3) MICROWAVES ABOVE THE REACH RANGES AND OPERATING
 PARTS OF THE 2017 FBC-ACCESSIBILITY CODE. SHEET
 014_A800 DETAIL 12 DOES INDICATE AN ADJUSTABLE SHELF TO
 HOLD MICROWAVES. PLEASE NOTE AT LEAST ONE OF THE
 MICROWAVES MUST COMPLY WITH THE 2017 FBC-ACCESSIBILITY
 CODE SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
 4) SHEET 012_A-102 FOR THE HAZARDOUS IV PREP, ANTI-ROOM
 AND NON-HAZARDOUS IV PREP ALL NEW WALLS ARE SHOWN WITH
 A WALL TAG 1E. SHEET 009-A003 THE PARTITION TYPES
 PROVIDES A CUT SECTION THROUGH PARTITION TYPE 1E THERE
 IS NO VERTICAL SECTION FOR THIS WALL SHOWING IF THIS IS
 A FIRE RATED WALL, SMOKE BARRIER, ETC. THERE ARE OTHER
 PERMITS FOR ON THIS FLOOR SHOWING THERE IS CANCER
 TREATMENT ON THIS FLOOR. THE INFUSION SUITE LEEDS US TO
 BELIEVE THIS AREA MAY BE USED FOR RENAL DIALYSIS CENTER
 AND WOULD BE COVERED UNDER THE FGI GUIDELINES BUT THE
 COVERSHEET DOES NOT INCLUDE THE SCOPE OF TREATMENT FOR
 THIS AREA. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
 THE FGI GUIDELINES SECTION 2.2-3.10 IS FOR CANCER
 TREATMENT/ INFUSION THERAPY SERVICE BUT THIS SECTION
 DOES NOT ADDRESS HAZARDOUS IV PREP ROOMS????AND THE
 RATING OF SUCH ROOM.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  