Plan Review Notes
Plan Review Notes For Permit 19020640
Permit Number 19020640
Review Stop E
Sequence Number 2
Notes
Date Text
2019-08-09 08:34:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. ELECTRICAL PLAN STATES: "FOR REFERENCE ONLY". PERMIT
 APPLICATION STATES THERE IS ELECTRICAL WORK TO BE
 COMPLETED, BUT PLAN PROVIDED DOES NOT PROPOSE ANY WORK.
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5 (THERE ARE 2 SHEETS
 IN THE PACKAGE FOR ELECTRICAL. ONE STILL STATES FOR
 REFERENCE ONLY. THE OTHER SHEET HAS A STATEMENT THAT IT
 IS PREPARED BY AN ENGINEER AND STATES UNAUTHORIZED
 DUPLICATION IS NOT PERMITTED, THIS SHEET IS SIGNED BY
 THE ELECTRICAL CONTRACTOR IN VIOLATION OF THIS
 STATEMENT. PROVIDE CORRECTION.)
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT ADDRESSED.)
  
 NEW COMMENTS:
  
 3. PLAN DOES NOT INDICATE WHAT IS EXISTING AND WHAT IS
 NEW. PROVIDE CLARIFICATION. WPB FBC 107.2.1
 4. AN AIC CALCULATION WAS PROVIDED, BUT THE SERVICE IS
 SHOWN AS EXISTING. IS THIS A NEW SERVICE? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1
 5. ARE THERE ANY LOADS BEING ADDED? SOME LOADS ARE
 LISTED, BUT NO LOAD CALCULATION IS PROVIDED. PROVIDE
 ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30
 6. FOR CHANGE OF OCCUPANCY, IF LIGHTS ARE BEING ADDED
 THE CODE REQUIRES AUTOMATIC CONTROL OF THE LIGHTING.
 PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
  
 FURTHER COMMENTS ARE POSSIBLE BASED ON THE RESPONSE
 RECEIVED FROM THESE COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  