| 2019-08-09 08:34:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. ELECTRICAL PLAN STATES: "FOR REFERENCE ONLY". PERMIT |
| | APPLICATION STATES THERE IS ELECTRICAL WORK TO BE |
| | COMPLETED, BUT PLAN PROVIDED DOES NOT PROPOSE ANY WORK. |
| | PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED |
| | BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 (THERE ARE 2 SHEETS |
| | IN THE PACKAGE FOR ELECTRICAL. ONE STILL STATES FOR |
| | REFERENCE ONLY. THE OTHER SHEET HAS A STATEMENT THAT IT |
| | IS PREPARED BY AN ENGINEER AND STATES UNAUTHORIZED |
| | DUPLICATION IS NOT PERMITTED, THIS SHEET IS SIGNED BY |
| | THE ELECTRICAL CONTRACTOR IN VIOLATION OF THIS |
| | STATEMENT. PROVIDE CORRECTION.) |
| | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 (NOT ADDRESSED.) |
| | |
| | NEW COMMENTS: |
| | |
| | 3. PLAN DOES NOT INDICATE WHAT IS EXISTING AND WHAT IS |
| | NEW. PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| | 4. AN AIC CALCULATION WAS PROVIDED, BUT THE SERVICE IS |
| | SHOWN AS EXISTING. IS THIS A NEW SERVICE? PROVIDE |
| | CLARIFICATION. WPB FBC 107.2.1 |
| | 5. ARE THERE ANY LOADS BEING ADDED? SOME LOADS ARE |
| | LISTED, BUT NO LOAD CALCULATION IS PROVIDED. PROVIDE |
| | ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING |
| | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS |
| | ADEQUATE. NEC 215.2, 220, 408.30 |
| | 6. FOR CHANGE OF OCCUPANCY, IF LIGHTS ARE BEING ADDED |
| | THE CODE REQUIRES AUTOMATIC CONTROL OF THE LIGHTING. |
| | PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | |
| | FURTHER COMMENTS ARE POSSIBLE BASED ON THE RESPONSE |
| | RECEIVED FROM THESE COMMENTS. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |