| 2019-03-11 10:12:51 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020640 |
| | 3/11/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW. |
| | PLEASE PROVIDE PLANS THAT CLEARLY SHOW THE SCOPE OF |
| | WORK FOR THE PROPOSED BUSINESS OFFICE- SECTION 107.1 |
| | WPB. |
| | |
| | 2) THE BUILDING PLANS EXAMINER HAS IDENTIFIED THE |
| | PROPOSED PROJECT AS A "CHANGE OF OCCUPANCY". PLEASE |
| | REFER TO SECTION 301.1 FBC EX AND INDICATE WHICH |
| | COMPLIANCE METHOD WILL BE APPLIED. PLEASE NOTE THAT IF |
| | CHOOSING THE WORK AREA METHOD (301.1.2) REFER TO |
| | SECTION 1009.1 FBC EX AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR THE SPACE- SEE TABLE 403.3.1.1 FBC M. |
| | |
| | 3) REFER TO SECTION C505.1 FBC EC AND VERIFY COMPLIANCE |
| | PETAINING TO CHANGES IN ENERGY DEMAND. PLEASE NOTE THAT |
| | NEW MECHANICAL AND ELECTRCAL LIGHTING CHANGES MAY |
| | INCREASE THE DEMAND. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |