Plan Review Notes
Plan Review Notes For Permit 19020631
Permit Number 19020631
Review Stop M
Sequence Number 1
Notes
Date Text
2019-03-11 09:19:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020631
 3/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GENERAL CONTRACTOR NEEDS TO CLARIFY WITH WPB
 BUILDING DEPT. IF THE PRIVATE PROVIDER WILL BE
 PROVIDING BOTH PLAN REVIEW AND INSPECTIONS ON THE
 PROPOSED PROJECT.
  
 2) SHEET GM401 OF THE MAIN GARAGE PLANS (PERMIT
 #18090262) SHOW THE CO AND NO2 SENSORS LOCATED IN THE
 BASEMENT LEVEL CONNECTING TO CONTROLLER SCD-103 TO
 ACTIVATE STROBE LIGHT ALARM DEVICES. PLEASE CLARIFY IF
 THIS SYSTEM IS CONNECTED TO THE MAIN FIRE ALARM SYSTEM.
 THE CONTROLLER IS NOT SHOWN ON THE PLAN (SHEET FA-02).
  
 3) PROVIDE A SUBMITTAL FOR THE LEAD ACID BATTERY
 CABINETS, AND REFER TO SECTION 502.5 FBC M. THE BATTERY
 CABINETS ARE REQUIRED TO BE VENTILATED IN ACCORDANCE
 WITH SECTION 502.5. THE CABINETS WERE NOT SHOWN ON THE
 MAIN MECHANICAL PLANS. PLEASE CONTACT THE GENERAL
 CONTRACTOR AND THE ENGINEER OF RECORD AS A REVISION TO
 THE MAIN PLANS MAY BE REQUIRED FOR THE VENTILATION
 SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  