2019-11-18 10:34:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
  
 NEW COMMENTS:
  
 3. PANEL C SHOWS CIRCUIT 40 AND 42 AS FEEDING A
 GENERATOR RECEPTACLE. THIS RECEPTACLE IS NOT SHOWN IN
 ANY OTHER LOCATION ON THE PLAN. WHAT IS THE PRURPOSE OF
 THIS RECEPTACLE? IF THIS IS A PLUG FOR A STAND BY
 GENERATOR, A MEANS TO ISOLATE THE GENERATOR FEED FROM
 THE POWER COMPANY FEED IS REQUIRED. PROVIDE CORRECTION.
 NEC 702.5
 4. RISER DIAGRAM SHOWS AN ATS WITH THE NOTE THAT AN ATS
 IS NOT EXISTING AND THIS IS A PASS THROUGH DEVICE ONLY.
 PROVIDE CLARIFICATION. WHAT TYPE OF DEVICE IS LOCATED
 HERE? IS THIS A JUNCTION BOX WITH PULL THROUGH WIRES
 ONLY, OR IS THERE SOME TYPE OF DEVICE HERE? LABEL
 CORRECTLY. WPB FBC 107.2.1
 5. WHY IS THERE A LOAD OF 10 KW SPECIFIED FOR THE
 GENERATOR RECEPTACLE? IS THIS AN ACTUAL LOAD, OR A
 GENERATOR FEEDING THE PANEL? PROVIDE ACCURATE LOAD
 CALCULATION. NEC 220; WPB FBC 107.2.1
 6. IF THIS IS A GENERATOR FEEDING THE PANEL, HOW WILL A
 SINGLE PHASE GENERATOR PROVIDE THE NECESSARY POWER FOR
 THREE PHASE LOADS? PROVIDE CLARIFICATION. NEC 110.3;
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved