| 2019-03-13 09:52:21 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) VALUE SEEMS LOW.BUILDING PERMIT VALUATIONS. IF, IN |
| | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION |
| | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE.. W.P.B AMEND TO THE FBC 109.3 |
| | |
| | 2) THESE PLANS ARE DIGITALLY SIGNED. ONLY PLANS |
| | SUBMITTED DIGITALLY ARE APPROVED TO BE SIGNED |
| | DIGITALLY. PLEASE HAVE PLANS WET SIGNED BY DESIGN |
| | PROFESSIONAL OF RECORD. F.S RULE 61G1-16.005 |
| | |
| | 3) SHT. D3 MASTER SHOWER IS MISSING FROM THE ISOMETRIC |
| | DRAWING. FBC 107.3.5 |
| | |
| | 4) SHT. D3 UPSTAIRS GUEST BATHROOM HAS 2 WET VENTED |
| | FIXTURES BEYOND THE WET VENT. ONLY 1 FIXTURE IS |
| | PERMITTED. FBC-R P3108.2.1 |
| | |
| | 5) THE 1ST BRANCH DRAIN THAT PICKS UP THE KITCHEN/ |
| | WASHING MACHINE IS 2" AND PER TABLE FBC-R P 3005.4.1 IS |
| | PERMITTED A MAX 6 DFU'S. PER TABLE FBC-R P3004.1 YOU |
| | CURRENTLY HAVE 7 DFU'S. PLEASE CHANGE PIPE SIZE TO 3" |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | |
| | SAMANTHA HILL |
| | CHIEF PLANS EXAMINER |
| | 561-805-6724 |