2019-03-13 09:52:21PLUMBING 1ST REVIEW**DENIED**
  
 1) VALUE SEEMS LOW.BUILDING PERMIT VALUATIONS. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE.. W.P.B AMEND TO THE FBC 109.3
  
 2) THESE PLANS ARE DIGITALLY SIGNED. ONLY PLANS
 SUBMITTED DIGITALLY ARE APPROVED TO BE SIGNED
 DIGITALLY. PLEASE HAVE PLANS WET SIGNED BY DESIGN
 PROFESSIONAL OF RECORD. F.S RULE 61G1-16.005
  
 3) SHT. D3 MASTER SHOWER IS MISSING FROM THE ISOMETRIC
 DRAWING. FBC 107.3.5
  
 4) SHT. D3 UPSTAIRS GUEST BATHROOM HAS 2 WET VENTED
 FIXTURES BEYOND THE WET VENT. ONLY 1 FIXTURE IS
 PERMITTED. FBC-R P3108.2.1
  
 5) THE 1ST BRANCH DRAIN THAT PICKS UP THE KITCHEN/
 WASHING MACHINE IS 2" AND PER TABLE FBC-R P 3005.4.1 IS
 PERMITTED A MAX 6 DFU'S. PER TABLE FBC-R P3004.1 YOU
 CURRENTLY HAVE 7 DFU'S. PLEASE CHANGE PIPE SIZE TO 3"
  
 TIM HUNT
 PLUMBING PLANS EXAMINER