| 2019-09-16 11:14:54 | 1) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 |
| | FBC-R SEC. G2413.4.1, G2413.4.2. THE FLAT DRAWING THAT |
| | HAS BEEN SUBMITTED IS UNACCEPTABLE AS IT IS EXTREMELY |
| | DIFFICULT TO TELL WHERE THE LINES START AND END. |
| | SEC.107.3.5.3 OF WPB AMEND. TO FBC. 2ND REQUEST. |
| | 2.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). 2ND REQUEST |
| | 3.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| | SEC. G 2413.4.1, G2413.4.2.2ND REQUEST. |
| | 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | THE GAS PLAN NOTES 5 PSI AND 1/2 LB. CLARIFY.2ND |
| | REQUEST. |
| | 5) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | THE ONLY GAS APPLIANCE ON THIS SYSTEM. IF NOT, SUBMIT A |
| | COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| | PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| | THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| | THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| | 6) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN |
| | SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| | OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC |
| | SEC. 107.2.1. 2ND REQUEST. THE FLOOR PLAN THAT WAS |
| | SUBMITTED NEEDS TO BE REDONE SO THAT IT CLEARLY |
| | REFLECTS THE LOCATION OF THE TANKLESS WATER HEATER.2ND |
| | REQUEST. |
| | 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3.2ND REQUEST. |
| | 8) THE PLANS INDICATE AN EXISTING GAS METER/LP TANK AND |
| | CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS |
| | ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST |
| | BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO |
| | ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF |
| | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1, |
| | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, |
| | G2413.2, G2413.2ND REQUEST. |
| | 9) SUBMIT ONE ADDITIONAL COPY OF THE INSTALLATION |
| | MANUAL. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) INDICATE ON THE MANUFACTURER'S SPECIFICATIONS WHICH |
| | MODEL OF THE WATER HEATER IS BEING INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 11) PLACE A NOTE ON THE PLAN HOW THE WINDOW IS |
| | NON-OPERATIONAL. SCREWING THE WINDOW SHUT IS NOT |
| | ACCEPTABLE. IF THIS IS A FIXED WINDOW, THEN NOTE SUCH |
| | ON THE PLANS. |
| | |