Plan Review Notes
Plan Review Notes For Permit 19020510
Permit Number 19020510
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-04 08:46:471) SHT. A-1 - "CODE REFERENCES" BOX NOTES THAT THIS IS
 AN R-3 OCCUPANCY.THIS SHOULDD BE CLASSIFIED AS AN R-2
 OCCUPANCY IN ACCORDANCE WITH 2014 FBC-BUILDING SEC.
 310.4. CLARIFY.
 2) THE PLANS SHALL BEAR THE SEAL AND WET SIGNATURE OF
 THE DESIGN PROFESSIONAL OF RECORD. THE PLANS HAVE A
 PRINTED DIGITAL SEAL ON THEM WHICH IS ONLY VALID FOR
 PLANS SUBMITTED IN DIGITAL FORMAT. FL. ADMIN. CODE RULE
 61G15-23.002.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  