| Plan Review Notes For Permit 19020481 |
| Permit Number |
19020481 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-14 08:02:43 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING (PREVIOUS REVIEW COMMENTS | | | WERE NOT ADDRESSED.) | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE RAS 117 CALCULATIONS ARE REQUIRED TO BE SIGNED | | | AND SEALED BY THE ENGINEER, TOMMY R. TAVERAS PE 60514. | | | THE RAS 117 CALCULATION DOCUMENTS ARE ON PAPER AND THEY | | | ARE STAMPED WITH A DIGITAL SIGNATURE. FAC 61G15-23.002 | | | REQUIRES THE ENGINEER'S HANDWRITTEN SIGNATURE AND SEAL | | | ON DOCUMENTS SUBMITTED FOR PUBLIC RECORD, DIGITAL | | | SIGNATURES ARE ONLY ACCEPTABLE ON ELECTRONICALLY | | | SUBMITTED DOCUMENTS PER FAC 61G15-23.003. | | | | | | 2) ONE OF THE A4.01 SHEETS IS MISSING FROM THE | | | DOCUMENTS. FBC 107.2.1 | | | |
|