| 2019-02-25 16:24:42 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE RAS 117 CALCULATIONS ARE REQUIRED TO BE SIGNED | | | AND SEALED BY THE ENGINEER, TOMMY R. TAVERAS PE 60514. | | | THE RAS 117 CALCULATION DOCUMENTS ARE ON PAPER AND THEY | | | ARE STAMPED WITH A DIGITAL SIGNATURE. FAC 61G15-23.002 | | | REQUIRES THE ENGINEER'S HANDWRITTEN SIGNATURE AND SEAL | | | ON DOCUMENTS SUBMITTED FOR PUBLIC RECORD, DIGITAL | | | SIGNATURES ARE ONLY ACCEPTABLE ON ELECTRONICALLY | | | SUBMITTED DOCUMENTS PER FAC 61G15-23.003. | | | |
|