Plan Review Notes
Plan Review Notes For Permit 19020481
Permit Number 19020481
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-25 16:24:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ENGINEER, TOMMY R. TAVERAS PE 60514.
 THE RAS 117 CALCULATION DOCUMENTS ARE ON PAPER AND THEY
 ARE STAMPED WITH A DIGITAL SIGNATURE. FAC 61G15-23.002
 REQUIRES THE ENGINEER'S HANDWRITTEN SIGNATURE AND SEAL
 ON DOCUMENTS SUBMITTED FOR PUBLIC RECORD, DIGITAL
 SIGNATURES ARE ONLY ACCEPTABLE ON ELECTRONICALLY
 SUBMITTED DOCUMENTS PER FAC 61G15-23.003.
  