Plan Review Notes
Plan Review Notes For Permit 19020470
Permit Number 19020470
Review Stop E
Sequence Number 2
Notes
Date Text
2019-04-05 12:41:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 COMMENT RESPONSE NOT RECEIVED, NO APPARENT CORRECTIONS
 PROVIDED. SEE PREVIOUS REVIEW BELOW AND ADDRESS.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
  
 1. NEED LOAD CALCULATION DONE IN ACCORDANCE WITH
 ARTICLE 220 OF THE NEC LOADS ON P4 OR P5 EXCEED RATING
 AND NOT ALL LOADS SHOWN.
  
 2. PANELS P4 AND P5 LOOK OVER LOADED PER LOADS SHOWN,
 CHECK ALL LOADS TO COORDINATE WITH ELECTRIC SHOWN ON
 DRAWINGS. 0 LOAD SHOWN ON PANEL SCHEDULE NOT
 ACCEPTABLE.
  
 3. ELECTRIC TO NEW NUCLEAR CAMERA ROOMS AR TREATMENT
 ROOMS AND SHALL BE TREATED AS SUCH 517.13(A)(B)
  
 4. RISER DIAGRAM NEEDED AND SIGN SHALL BE POSTED AT
 EACH PANEL SHOWING WHERE IT IS FED FROM 408.4 PLEASE
 SHOW NOTE ON PLANS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER