| Plan Review Notes For Permit 19020470 |
| Permit Number |
19020470 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-26 08:24:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED LOAD CALCULATION DONE IN ACCORDANCE WITH ARTICLE | | | 220 OF THE NEC LOADS ON P4 OR P5 EXCEED RATING AND NOT | | | ALL LOADS SHOWN. | | | | | | PANELS P4 AND P5 LOOK OVER LOADED PER LOADS SHOWN, | | | CHECK ALL LOADS TO CORODINATE WITH ELECTRIC SHOWN ON | | | DRAWINGS 0 LOAD ON PANEL SCHEDULE NOT ACCEPTABLE. | | | | | | ELECTRIC TO NEW NUCLEAR CAMERA ROOMS AR TREATMENT ROOMS | | | AND SHALL BE TREATED AS SUCH 517.13(A)(B) | | | | | | RISER DIAGRAM NEEDED AND SIGN SHALL BE POSTED AT EACH | | | PANEL SHOWING WHERE IT IS FED FROM 408.4 PLEASE SHOW | | | NOTE ON PLANS . |
|