Plan Review Notes
Plan Review Notes For Permit 19020470
Permit Number 19020470
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-26 08:24:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED LOAD CALCULATION DONE IN ACCORDANCE WITH ARTICLE
 220 OF THE NEC LOADS ON P4 OR P5 EXCEED RATING AND NOT
 ALL LOADS SHOWN.
  
 PANELS P4 AND P5 LOOK OVER LOADED PER LOADS SHOWN,
 CHECK ALL LOADS TO CORODINATE WITH ELECTRIC SHOWN ON
 DRAWINGS 0 LOAD ON PANEL SCHEDULE NOT ACCEPTABLE.
  
 ELECTRIC TO NEW NUCLEAR CAMERA ROOMS AR TREATMENT ROOMS
 AND SHALL BE TREATED AS SUCH 517.13(A)(B)
  
 RISER DIAGRAM NEEDED AND SIGN SHALL BE POSTED AT EACH
 PANEL SHOWING WHERE IT IS FED FROM 408.4 PLEASE SHOW
 NOTE ON PLANS .