| 2019-04-12 16:52:55 | GAS PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. REFERENCE PLAN PAGE P-1. RE-NAME PLUMBING CONNECTION |
| | SCHEDULE TO GAS EQUIPMENT SCHEDULE. |
| | |
| | 2. LIST ALL GAS EQUIPMENT ON SCHEDULE. PLAN PAGE A-2 |
| | SHOWS A GAS WATER HEATER. ARE THERE ANY MORE GAS |
| | APPLIANCES? |
| | |
| | 3. STATE CORRECT GAS PIPING TABLE ON GAS PIPING |
| | CALCULATION SCHEDULE. THIS IS A RESIDENTIAL PROPERTY, |
| | TABLE SHOULD BE G2413.4 (1). |
| | |
| | 4. PROVIDE COMBUSTION AIR CALCULATIONS PER G2407.1. |
| | |
| | 5. PROVIDE VENTING DETAIL PER G2427. |
| | |
| | 6. SHUTOFF REQUIRED PRIOR TO GAS LINE ENTERING THE |
| | BUILDING. |
| | |
| | 7. PROVIDE DRIPLEG DETAIL AT APPLIANCES PER G2419. |
| | |
| | 8. GASS RISER DIAGRAHM SHOWS TWO SHUTOFFS AT APPLIANCE |
| | LOCATION. IS ONE OF THESE A REGULATOR? PLEASE CLARIFY. |
| | |
| | CANNOT VERIFY PIPING SIZE UNTIL TOTAL BTU LAOD AND |
| | TOTAL PIPING LENGTH HAVE BEEN PROVIDED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |