Plan Review Notes
Plan Review Notes For Permit 19020469
Permit Number 19020469
Review Stop G
Sequence Number 2
Notes
Date Text
2019-04-12 16:52:55GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REFERENCE PLAN PAGE P-1. RE-NAME PLUMBING CONNECTION
 SCHEDULE TO GAS EQUIPMENT SCHEDULE.
  
 2. LIST ALL GAS EQUIPMENT ON SCHEDULE. PLAN PAGE A-2
 SHOWS A GAS WATER HEATER. ARE THERE ANY MORE GAS
 APPLIANCES?
  
 3. STATE CORRECT GAS PIPING TABLE ON GAS PIPING
 CALCULATION SCHEDULE. THIS IS A RESIDENTIAL PROPERTY,
 TABLE SHOULD BE G2413.4 (1).
  
 4. PROVIDE COMBUSTION AIR CALCULATIONS PER G2407.1.
  
 5. PROVIDE VENTING DETAIL PER G2427.
  
 6. SHUTOFF REQUIRED PRIOR TO GAS LINE ENTERING THE
 BUILDING.
  
 7. PROVIDE DRIPLEG DETAIL AT APPLIANCES PER G2419.
  
 8. GASS RISER DIAGRAHM SHOWS TWO SHUTOFFS AT APPLIANCE
 LOCATION. IS ONE OF THESE A REGULATOR? PLEASE CLARIFY.
  
 CANNOT VERIFY PIPING SIZE UNTIL TOTAL BTU LAOD AND
 TOTAL PIPING LENGTH HAVE BEEN PROVIDED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  