| 2019-02-26 12:34:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. ALL LOADS ARE NOT SHOWN IN CALCULATION |
| | PROVIDED. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 2. SCOPE OF WORK STATES THAT MAIN DISCONNECT IS NEW, |
| | BUT THE RISER SHOWS THIS AS EXISTING. PROVIDE |
| | CLARIFICATION AND/OR CORRECTION. NEC 215.5; WPB FBC |
| | 107.2.1 |
| | 3. IF SERVICE IS BEING REPLACED OR RE-WORKED, PROVIDE |
| | AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE |
| | E3606.3 |
| | 4. NOTE STATES THAT ALL REEPTACLES SHALL BE TAMPER |
| | RESISTANT PER THE 2011 NEC, WHICH IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE |
| | 5. PROVIDE LOCATION OF ELECTRICAL SERVICE ON PLAN. WPB |
| | FBC 107.2.1 |
| | 6. PANEL SCHEDULES SHOW ONE ASTERISK FOR ARC FAULT |
| | CIRCUIT, AND THE SHOWS TWO ASTERISK FOR THE SAME THING. |
| | WHICH IS IT? PROVIDE CLARIFICATION AND CORRECT |
| | DISCREPANCY. |
| | 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| | FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |