| 2019-04-22 11:45:06 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED |
| | |
| | 2) NOT ADDRESSED. THE DETAILS ON SHEET C4 DO NOT |
| | PROVIDE THE REQUIRED ANCHORING DETAILS FOR THE EXTERIOR |
| | ANTENNA AND THE NOTE STATES THAT THE STRUCTURAL |
| | ANALYSIS WAS PREFORMED BY OTHERS. SUBMIT A SIGNED AND |
| | SEALED STRUCTURAL ANALYSIS OF THE ANTENNA MOUNT AND |
| | REQUIRED ANCHORS THAT ARE ADEQUATE TO RESIST THE WIND |
| | LOADS. FBC 1604.1 |
| | BOTH THE PLANS AND THE STRUCTURAL ANALYSIS THAT WAS |
| | SUBMITTED FAIL TO PROVIDE THE DETAILS ON THE PROPOSED |
| | WEDGE ANCHORS. THE STRUCTURAL ANALYSIS NEEDS TO SPECIFY |
| | THE ANCHOR SIZE AND THE EMBEDMENT DEPTH OF THE WEDGE |
| | ANCHORS, IF A WASHER IS REQUIRED AS WELL AS THE |
| | REQUIRED PSI VALUE OF THE CONCRETE SUBSTRATE. FBC |
| | 107.2.1.2 |
| | |
| | 3) PARTIALLY ADDRESSED. THE FIRESTOP DETAIL 1 ON SHEET |
| | C6, FOR CONCRETE PENETRATIONS HAS A T RATING OF 0 HRS. |
| | FBC 714.4.1.2 REQUIRES FLOOR/CEILING |
| | THROUGH-PENETRATIONS TO HAVE A T RATING OF NOT LESS |
| | THAN 1 HR. BUT NOT LESS THAN THE REQUIRED RATING OF THE |
| | FLOOR PENETRATED. |
| | THE PLANS STILL HAVE THE DETAIL WITH NO T RATING. IN |
| | ORDER TO PREVENT CONFUSION IN THE FIELD, THIS NEEDS BE |
| | REMOVED FROM THE PLANS AND REPLACED BY THE ASSEMBLY |
| | WITH THE T RATING THAT WAS SUBMITTED WITH THE |
| | DOCUMENTS. |
| | |
| | |