Plan Review Notes
Plan Review Notes For Permit 19020417
Permit Number 19020417
Review Stop B
Sequence Number 2
Notes
Date Text
2019-04-22 11:45:06PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED
  
 2) NOT ADDRESSED. THE DETAILS ON SHEET C4 DO NOT
 PROVIDE THE REQUIRED ANCHORING DETAILS FOR THE EXTERIOR
 ANTENNA AND THE NOTE STATES THAT THE STRUCTURAL
 ANALYSIS WAS PREFORMED BY OTHERS. SUBMIT A SIGNED AND
 SEALED STRUCTURAL ANALYSIS OF THE ANTENNA MOUNT AND
 REQUIRED ANCHORS THAT ARE ADEQUATE TO RESIST THE WIND
 LOADS. FBC 1604.1
 BOTH THE PLANS AND THE STRUCTURAL ANALYSIS THAT WAS
 SUBMITTED FAIL TO PROVIDE THE DETAILS ON THE PROPOSED
 WEDGE ANCHORS. THE STRUCTURAL ANALYSIS NEEDS TO SPECIFY
 THE ANCHOR SIZE AND THE EMBEDMENT DEPTH OF THE WEDGE
 ANCHORS, IF A WASHER IS REQUIRED AS WELL AS THE
 REQUIRED PSI VALUE OF THE CONCRETE SUBSTRATE. FBC
 107.2.1.2
  
 3) PARTIALLY ADDRESSED. THE FIRESTOP DETAIL 1 ON SHEET
 C6, FOR CONCRETE PENETRATIONS HAS A T RATING OF 0 HRS.
 FBC 714.4.1.2 REQUIRES FLOOR/CEILING
 THROUGH-PENETRATIONS TO HAVE A T RATING OF NOT LESS
 THAN 1 HR. BUT NOT LESS THAN THE REQUIRED RATING OF THE
 FLOOR PENETRATED.
 THE PLANS STILL HAVE THE DETAIL WITH NO T RATING. IN
 ORDER TO PREVENT CONFUSION IN THE FIELD, THIS NEEDS BE
 REMOVED FROM THE PLANS AND REPLACED BY THE ASSEMBLY
 WITH THE T RATING THAT WAS SUBMITTED WITH THE
 DOCUMENTS.
  
  