2019-03-12 16:51:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ELECTRONICALLY SUBMITTED PLANS ARE REQUIRED TO BE
 DIGITALLY SIGNED BY THE FLORIDA P.E. PER FS 471 & FAC
 61G15-23.003.
  
 2) THE DETAILS ON SHEET C4 DO NOT PROVIDE THE REQUIRED
 ANCHORING DETAILS FOR THE EXTERIOR ANTENNA AND THE NOTE
 STATES THAT THE STRUCTURAL ANALYSIS WAS PREFORMED BY
 OTHERS. SUBMIT A SIGNED AND SEALED STRUCTURAL ANALYSIS
 OF THE ANTENNA MOUNT AND REQUIRED ANCHORS THAT ARE
 ADEQUATE TO RESIST THE WIND LOADS. FBC 1604.1
  
 3) THE FIRESTOP DETAIL 1 ON SHEET C6, FOR CONCRETE
 PENETRATIONS HAS A T RATING OF 0 HRS. FBC 714.4.1.2
 REQUIRES FLOOR/CEILING THROUGH-PENETRATIONS TO HAVE A T
 RATING OF NOT LESS THAN 1 HR. BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR PENETRATED.
  
  
  
  
  
2019-02-27 08:24:23SEE HIGHLIGHTED NOTE ON PAGE C4, LET ME KNOW IF YOU
 PASS PLAN JLEAHY