| Plan Review Notes For Permit 19020417 |
| Permit Number |
19020417 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-12 16:51:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ELECTRONICALLY SUBMITTED PLANS ARE REQUIRED TO BE | | | DIGITALLY SIGNED BY THE FLORIDA P.E. PER FS 471 & FAC | | | 61G15-23.003. | | | | | | 2) THE DETAILS ON SHEET C4 DO NOT PROVIDE THE REQUIRED | | | ANCHORING DETAILS FOR THE EXTERIOR ANTENNA AND THE NOTE | | | STATES THAT THE STRUCTURAL ANALYSIS WAS PREFORMED BY | | | OTHERS. SUBMIT A SIGNED AND SEALED STRUCTURAL ANALYSIS | | | OF THE ANTENNA MOUNT AND REQUIRED ANCHORS THAT ARE | | | ADEQUATE TO RESIST THE WIND LOADS. FBC 1604.1 | | | | | | 3) THE FIRESTOP DETAIL 1 ON SHEET C6, FOR CONCRETE | | | PENETRATIONS HAS A T RATING OF 0 HRS. FBC 714.4.1.2 | | | REQUIRES FLOOR/CEILING THROUGH-PENETRATIONS TO HAVE A T | | | RATING OF NOT LESS THAN 1 HR. BUT NOT LESS THAN THE | | | REQUIRED RATING OF THE FLOOR PENETRATED. | | | | | | | | | | | | | | | | | 2019-02-27 08:24:23 | SEE HIGHLIGHTED NOTE ON PAGE C4, LET ME KNOW IF YOU | | | PASS PLAN JLEAHY |
|