| 2021-12-06 14:39:37 | FAILED |
| | |
| | 1) THE SURVEY PROVIDED WITH THE APPLICATION DOES NOT |
| | COVER THE ENTIRE SCOPE OF WORK, SPECIFICALLY THE SOUTH |
| | WEST CORNER OF THE INTERSECTION OF EVERNIA STREET AND |
| | FLAGLER DRIVE. THIS SECTION OF THE INTERSECTION CALLS |
| | OUT A PROPOSED BORE PIT AND HANDHOLE FOR THE |
| | UNDERGROUND POWER. THE SURVEY NEEDS TO BE PROVIDED SO |
| | THAT STAFF CAN VERIFY THAT THE INSTALLATIONS ARE FULLY |
| | WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. |
| | |
| | 2) THE POLE NEEDS TO BE IN LINE WITH PALM TREES ALONG |
| | DATURA STREET. PLEASE NOTE THE OUTSIDE EDGE OF THE POLE |
| | MUST BE SETBACK A MINIMUM OF 18 INCHES FROM THE CURB. |
| | |
| | 3) PROVIDE THE DIMENSIONS FROM THE EDGE OF THE |
| | EXCAVATION PIT FOR THE PROPOSED HANDHOLE WITHIN THE |
| | FLAGLER DRIVE RIGHT-OF-WAY, GENERALLY MIDWAY BETWEEN |
| | DATURA AND EVERNIA STREETS, TO THE TRUNK OF THE |
| | ADJACENT PALM TREES. THIS DIMENSION SHALL BE NO LESS |
| | THAN 5 FEET. |
| | |
| | 4) THE PLANS MUST CLEARLY CALL OUT THAT THE BORE, AND |
| | THUS THE BORE EQUIPMENT STAGING, IS DONE FROM THE BORE |
| | PITS ALONG FLAGLER DRIVE. THE BORE EQUIPMENT MAY NOT BE |
| | STAGED ADJACENT TO A PALM TREE (AT THE POLE OR AT THE |
| | HANDHOLE) SO AS NOT TO DAMAGE THE TREES. |
| | |
| | 5) THE POLE DESIGN AND THE UNDERGROUND FIBER PATH/DEPTH |
| | COMPLY WITH CITY REQUIREMENTS. |
| | |
| | 6) THE POLE COLOR SHALL BE GREY TO MATCH THE DECORATIVE |
| | LIGHT POLES ALONG DATURA STREET. |
| | |