| 2022-03-15 08:41:21 | INSUFFICIENT |
| | |
| | 1) WHEN THIS LOCATION WAS ORIGINALLY SUBMITTED TO THE |
| | CITY IN 2019, STAFF PROVIDED THE FOLLOWING COMMENT, "IN |
| | ACCORDANCE WITH SECTIONS 78-402(B) AND 78-411(B)(4) OF |
| | THE CITY OF WEST PALM BEACH CODE OF ORDINANCES, THE |
| | CITY OF WEST PALM BEACH IS REQUESTING THAT THIS |
| | PROPOSED SMALL WIRELESS FACILITY BE MOVED TO ANOTHER |
| | LOCATION IN THE RIGHT-OF-WAY AND PLACED ON AN |
| | ALTERNATIVE UTILITY POLE OR ON A NEW UTILITY POLE TO BE |
| | INSTALLED WITHIN THE RIGHT-OF-WAY." THERE WAS NO |
| | DISCUSSION REGARDING AN ALTERNATIVE LOCATION. STAFF HAS |
| | BEEN IN DISCUSSION WITH THE RELATED COMPANY, DEVELOPER |
| | OF THE ADJOINING PROPERTIES, SINCE THIS LOCATION WAS |
| | ORIGINALLY PROPOSED. THEY WOULD LIKE TO BE INVOLVED IN |
| | THE ALTERNATIVE SITING LOCATION SO THAT THE PROPOSED |
| | POLE LOCATION DOES NOT CONFLICT WITH THE REDEVELOPMENT |
| | OF ROSEMARY SQUARE. PLEASE REACH OUT TO DAVID HARRISON |
| | AT THE CONTACT BELOW TO BEGIN DISCUSSIONS. |
| | |
| | DAVID HARRISON |
| | VICE PRESIDENT |
| | DESIGN AND CONSTRUCTION |
| | |
| | RELATED COMPANIES |
| | 501 FERN STREET, SUITE 105 |
| | WEST PALM BEACH, FL 33401 |
| | (561) 570-3352 OFFICE |
| | |
| | 2) THE SURVEY AND ENGINEERING PLAN PROVIDED WITH THE |
| | APPLICATION INCORRECTLY SHOW THE SIDEWALK WIDTH AND |
| | THUS TRAVEL LANE CURB. STAFF HAS SURVEYS FROM WHEN |
| | RELATED RECONSTRUCTED HIBISCUS STREET WHICH SHOW THE |
| | SIDEWALK AT APPROXIMATELY 15 FEET IN WIDTH. THE |
| | PROPOSED POLE LOCATION AT 8.75 IS IN THE VALET DROP OFF |
| | AREA. |
| | |
| | 3) THE SURVEY CALLS OUT INCORRECT OWNERSHIP INFORMATION |
| | IN THE AREA AND STATES THE PROPOSED POLE HEIGHT AT ZERO |
| | FEET. THE SURVEY NEEDS TO SHOW ACCURATE INFORMATION. |
| | |
| | 4) THE EXISTING DECORATIVE LIGHT SHOWN ON THE SURVEY IS |
| | 17 FEET TALL (CITY CODE REQUIREMENT FOR HIBISCUS |
| | STREET). THE OVERALL FACILITY HEIGHT IS 24 FEET IN |
| | HEIGHT, WHICH EXCEEDS THE ALLOWANCE LISTED IN SECTION |
| | 94-411(G)(1) OF THE CITY CODE. |
| | |
| | 5) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC |
| | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH |
| | EXISTING UTILITIES. |
| | |
| | 6) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE |
| | COLOR IN THIS AREA SHALL BE RAL/RAYCAP 7022 UMBRA GREY. |
| | |