| 2019-03-05 10:06:52 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020381 |
| | ADD: 2970 N MILITARY TRAIL / DUMPSTER ENCLOSURE/ |
| | ANNEXATION IN PROGRESS |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: ??????????????? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 5/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THIS PERMIT APPLICATION FOR A DUMPSTER ENCLOSURE IS |
| | FOR A PROPERTY BEING ANNEXED INTO THE CITY OF WEST PALM |
| | BEACH. NO PERMIT CAN BE ISSUED UNTIL THIS PROCESS IS |
| | COMPLETE. THE OTHER ISSUE IS A CONTRACTOR WILL NEED TO |
| | SIGN ON AS THE CONTRACTOR OF RECORD FOR THE REMOVAL OF |
| | THIS BUILDING. 2017 FLORIDA BUILDING CODE W 2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION 105.1 REQUIRED. |
| | |
| | 2) ALL FOUR SHEETS THAT WERE UPLOADED FOR CITY |
| | DOCUMENTS FOR REVIEW APPEAR TO BE PAPER PLANS THAT WERE |
| | SCANNED INTO THE COMPUTER, SHEETS SP.1, SP.3, A010 |
| | DUMPSTER ENCLOSURE & A011 DUMPSTER ENCLOSURE DETAILS, |
| | NONE HAVE ELECTRONIC SIGNATURES. |
| | |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3) NEITHER SHEET A010 OR A011 INDICATE TO WHAT CODE |
| | THIS ENCLOSURE WAS DESIGNED. |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | CODE EDITION |
| | |
| | 4) NEITHER SHEET A010 OR A011 INDICATE TO WHAT WIND |
| | SPEED AND CRITERIA THE DUMPSTER ENCLOSURE WAS DESIGNED. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 4.2. RISK CATEGORY. |
| | |
| | 4.3TABLE 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE |
| | 30.3.1. |
| | |
| | 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 5) SHEET 004_A011 IN DETAILS 1-3 SHOWS THE OVERALL |
| | VERTICAL DIMENSION OF THE FOOTING BUT DOES NOT PROVIDE |
| | THE MINIMUM EMBEDMENT OF THE FOOTING. SEE 2017 FBC-B |
| | MINIMUM EMBEDMENT OF 12 INCHES BELOW GRADE. |
| | |
| | 6 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |