| 2020-03-26 11:40:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 19020380 2970 N MILITARY TRAIL |
| | |
| | PLUMBING COMMEMTS: APPROVED WITH PROVISO |
| | |
| | PLUMBING PROVISO: |
| | REVISION REQUIRED; REGARDING PLAN SHEETS C8, C8.1 AND |
| | SD1. REVISION SHALL BE SUBMITTED, APPROVED AND IN PLACE |
| | PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK. |
| | |
| | PROVIDE DEDICATED BACKFLOW PREVENTER IN SUPPLY LINE |
| | UPSTREAM OF THE YARD HYDRANTS |
| | PROVIDE LOCATION, DETAIL AND SPECIFICATION FOR SAID |
| | BACKFLOW PREVENTER. |
| | PROVIDE THE FOLLOWING |
| | A. SD1/DETAIL 12. IN ACCORDANCE WITH FBC 608.7, 608.8.1 |
| | AND 608.8.2, PROVIDE A BACKFLOW PREVENTER FOR THE |
| | DEDICATED SUPPLY, SIGNAGE AT THE HYDRANTS AND EXPOSED |
| | PIPING SHALL BE COLOR PURPLE AND LABELED. |
| | 1) FBC PL 608.7 VALVES AND OUTLETS PROHIBITED BELOW |
| | GRADE. FREEZEPROOF YARD HYDRANTS THAT DRAIN THE RISER |
| | INTO THE GROUND SHALL BE PERMITTED TO BE INSTALLED, |
| | PROVIDED THAT THE POTABLE WATER SUPPLY TO SUCH HYDRANTS |
| | IS PROTECTED UPSTREAM OF THE HYDRANTS IN ACCORDANCE |
| | WITH SECTION 608 AND THE HYDRANTS ARE PERMANENTLY |
| | IDENTIFIED AS NON-POTABLE OUTLETS BY APPROVED SIGNAGE |
| | THAT READS AS FOLLOWS: ?CAUTION, NON-POTABLE WATER. DO |
| | NOT DRINK.? |
| | A.FBC PL608.8.1 SIGNAGE REQUIRED. |
| | NONPOTABLE WATER OUTLETS, SUCH AS HOSE CONNECTIONS, |
| | OPEN ENDED PIPES AND FAUCETS, SHALL BE IDENTIFIED WITH |
| | SIGNAGE THAT READS AS FOLLOWS: ?NON-POTABLE WATER IS |
| | UTILIZED FOR [APPLICATION NAME]. CAUTION: NONPOTABLE |
| | WATER ? DO NOT DRINK.? THE WORDS SHALL BE LEGIBLY AND |
| | INDELIBLY PRINTED ON A TAG OR SIGN CONSTRUCTED OF |
| | CORROSION-RESISTANT WATERPROOF MATERIAL OR SHALL BE |
| | INDELIBLY PRINTED ON THE FIXTURE. THE LETTERS OF THE |
| | WORDS SHALL BE NOT LESS THAN 0.5 INCH (12.7 MM) IN |
| | HEIGHT AND IN COLORS IN CONTRAST TO THE BACKGROUND ON |
| | WHICH THEY ARE APPLIED. IN ADDITION TO THE REQUIRED |
| | WORDAGE, THE PICTOGRAPH SHOWN IN FBC PL FIGURE 608.8.1 |
| | SHALL APPEAR ON THE REQUIRED SIGNAGE. |
| | B. FBC PL 608.8.2 DISTRIBUTION PIPE LABELING AND |
| | MARKING. |
| | C. NON-POTABLE DISTRIBUTION PIPING SHALL BE PURPLE IN |
| | COLOR AND SHALL BE EMBOSSED, OR INTEGRALLY STAMPED OR |
| | MARKED, WITH THE WORDS: ?CAUTION: NONPOTABLE WATER ? DO |
| | NOT DRINK? OR THE PIPING SHALL BE INSTALLED WITH A |
| | PURPLE IDENTIFICATION TAPE OR WRAP. PIPE IDENTIFICATION |
| | SHALL INCLUDE THE CONTENTS OF THE PIPING SYSTEM AND AN |
| | ARROW INDICATING THE DIRECTION OF FLOW. HAZARDOUS |
| | PIPING SYSTEMS SHALL ALSO CONTAIN INFORMATION |
| | ADDRESSING THE NATURE OF THE HAZARD. PIPE |
| | IDENTIFICATION SHALL BE REPEATED AT INTERVALS NOT |
| | EXCEEDING 25 FEET AND AT EACH POINT WHERE THE PIPING |
| | PASSES THROUGH A WALL, FLOOR OR ROOF. LETTERING SHALL |
| | BE READILY OBSERVABLE WITHIN THE ROOM OR SPACE WHERE |
| | THE PIPING IS LOCATED. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | |
| | |
| | 19020380 2970 N MILITARY TRAIL |
| | |