| 2019-07-25 15:20:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | |
| | 2ND REQUEST |
| | 1. SEE MARK UPS ON PLAN SHEET C8 AND SD1; THESE ITEMS |
| | MUST BE SATISFACTORILY ADDRESSED BEFORE A PLUMBING |
| | PERMIT WILL BE ISSUED. |
| | A. C8 AND SD1/DETAIL 12: SD1/DETAIL 12 CREATES A |
| | HAZARDOUS CONDITION. IN ACCORDANCE WITH FBC 608.7, |
| | 608.8.1 AND 608.8.2, PROVIDE A BACKFLOW PREVENTER FOR |
| | THE DEDICATED SUPPLY, SIGNAGE AT THE HYDRANTS AND |
| | EXPOSED PIPING SHALL BE COLOR PURPLE AND LABELED. |
| | 1) FBC PL 608.7 VALVES AND OUTLETS PROHIBITED BELOW |
| | GRADE.FREEZEPROOF YARD HYDRANTS THAT DRAIN THE RISER |
| | INTO THE GROUND SHALL BE PERMITTED TO BE INSTALLED, |
| | PROVIDED THAT THE POTABLE WATER SUPPLY TO SUCH HYDRANTS |
| | IS PROTECTED UPSTREAM OF THE HYDRANTS IN ACCORDANCE |
| | WITH SECTION 608 AND THE HYDRANTS ARE PERMANENTLY |
| | IDENTIFIED AS NON-POTABLE OUTLETS BY APPROVED SIGNAGE |
| | THAT READS AS FOLLOWS: ?CAUTION, NON-POTABLE WATER. DO |
| | NOT DRINK.? |
| | A.FBC PL608.8.1SIGNAGE REQUIRED. |
| | NONPOTABLE WATER OUTLETS, SUCH AS HOSE CONNECTIONS, |
| | OPEN ENDED PIPES AND FAUCETS, SHALL BE IDENTIFIED WITH |
| | SIGNAGE THAT READS AS FOLLOWS: ?NON-POTABLE WATER IS |
| | UTILIZED FOR [APPLICATION NAME]. CAUTION: NONPOTABLE |
| | WATER ? DO NOT DRINK.? THE WORDS SHALL BE LEGIBLY AND |
| | INDELIBLY PRINTED ON A TAG OR SIGN CONSTRUCTED OF |
| | CORROSION-RESISTANT WATERPROOF MATERIAL OR SHALL BE |
| | INDELIBLY PRINTED ON THE FIXTURE. THE LETTERS OF THE |
| | WORDS SHALL BE NOT LESS THAN 0.5 INCH (12.7 MM) IN |
| | HEIGHT AND IN COLORS IN CONTRAST TO THE BACKGROUND ON |
| | WHICH THEY ARE APPLIED. IN ADDITION TO THE REQUIRED |
| | WORDAGE, THE PICTOGRAPH SHOWN IN FBC PL FIGURE 608.8.1 |
| | SHALL APPEAR ON THE REQUIRED SIGNAGE. |
| | B. FBC PL 608.8.2 DISTRIBUTION PIPE LABELING AND |
| | MARKING. |
| | C. NON-POTABLE DISTRIBUTION PIPING SHALL BE PURPLE IN |
| | COLOR AND SHALL BE EMBOSSED, OR INTEGRALLY STAMPED OR |
| | MARKED, WITH THE WORDS: ?CAUTION: NONPOTABLE WATER ? DO |
| | NOT DRINK? OR THE PIPING SHALL BE INSTALLED WITH A |
| | PURPLE IDENTIFICATION TAPE OR WRAP. PIPE IDENTIFICATION |
| | SHALL INCLUDE THE CONTENTS OF THE PIPING SYSTEM AND AN |
| | ARROW INDICATING THE DIRECTION OF FLOW. HAZARDOUS |
| | PIPING SYSTEMS SHALL ALSO CONTAIN INFORMATION |
| | ADDRESSING THE NATURE OF THE HAZARD. PIPE |
| | IDENTIFICATION SHALL BE REPEATED AT INTERVALS NOT |
| | EXCEEDING 25 FEET (7620 MM) AND AT EACH POINT WHERE THE |
| | PIPING PASSES THROUGH A WALL, FLOOR OR ROOF. LETTERING |
| | SHALL BE READILY OBSERVABLE WITHIN THE ROOM OR SPACE |
| | WHERE THE PIPING IS LOCATED. |
| | B.ADDITIONAL COMMENT: PER WPB FBC 1097.2.1, ADD SPEC |
| | AND DETAIL FOR BACKFLOW PREVENTER AND SHOW LOCATION ON |
| | THE PLAN |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE NOTE ON CIVIL DRAWINGS |
| | C8 THROUGH C.10 STATING ?PALM BEACH COUNTY WATER |
| | UTILITIES DEPARTMENT IS THE AUTHORITY HAVING |
| | JURISDICTION?, IF THAT IS INDEED THE CASE. IF NOT, THEN |
| | THE WEST PALM BEACH PUBLIC UTILITIES DEPARTMENT SHALL |
| | BE NOTED AND ALL REFERENCES TO PBC WUD SHALL BE |
| | REPLACED BY WPB PUD AND DETAILS SHALL REFLECT WPB PUD |
| | REQUIREMENTS. |
| | IF PBC WUD IS TO PREVAIL, CROSS OUT ALL DETAILS |
| | CONCERNING INTERCEPTORS AND BACKFLOW PREVENTERS THAT DO |
| | NOT APPLY TO THE PROJECT. |
| | |
| | 3. 2ND REQUEST FOR MANUFACTURER?S DATA SHEETS WHICH WAS |
| | FOR THE MOST PART COMPLIED WITH BUT STILL MISSING THE |
| | FOLLOWING: |
| | A. 3016/RINSE-O-MATIC |
| | B. 4025/FROZEN YOGURT DISPENSER |
| | C. 3005/POST MIX SODA SYSTEM |
| | |
| | 4. 2ND REQUEST: P430/DETAIL 6 NON FREEZE ROOF HYDRANT: |
| | PLEASE SPECIFY A MANUFACTURER/MODEL NUMBER WHICH |
| | INCLUDES A VACUUM BREAKER. RESPONSE LETTER SAID THIS |
| | WAS CORRECTED BUT I DO NOT SEE IT. PLEASE CLARIFY. |
| | ADDITIONALLY, PROVIDE NOTE ?PROVIDE DRAIN PIPE FROM |
| | 1/8? DRAIN HOLE AND DISCHARGE TO MOP SINK OR OTHER |
| | SUITABLE RECEPTACLE THROUGH AN AIR GAP? |
| | |
| | 5. P430; DETAIL 5 |
| | PER FBC PL 608.3, RELOCATE THE MOST UPSTREAM RPZ TO THE |
| | BRANCH PIPE BETWEEN THE TEE AND THE FILTER. |
| | |
| | 6. P430; DETAIL 5 |
| | WHAT DOES THE VALVED 2? PIPE FEEDING DOWN INTO THE |
| | GROUND SERVICE? |
| | |
| | 7. P430; DETAIL 5 |
| | PER WPB FBC 107.2.1, CLARIFY WHETHER OR NOT THE 2? RPZ |
| | WILL BE INSIDE AS SHOWN OR OUTSIDE ADJACENT TO THE |
| | METER |
| | |
| | 8. P431; DETAIL 4. |
| | A. PER FBC PL 1002.4.1, DEEP SEAL TRAP TRAPS ARE NOT |
| | PERMITTED. |
| | B. PER FBC PL 915.2.5, THE FIXTURE BRANCH OR FIXTURE |
| | DRAIN SHALL CONNECT TO THE COMBINATION WASTE AND VENT |
| | WITHIN A DISTANCE SPECIFIED IN TABLE 909.1. THE |
| | COMBINATION WASTE AND VENT PIPE SHALL BE CONSIDERED THE |
| | VENT FOR THE FIXTURE. |
| | |
| | 9. P431; DETAIL 6 AND PLAN SHEET P110 |
| | PER FBC PL 1002.4.1, PROVIDE TRAP PRIMER TO FLOOR SINK |
| | INSTALLED FOR FUTURE USE. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | PLEASE NOTE THE FOLLOWING: |
| | A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND |
| | DISPOSITION OF EXISTING FUEL TANKS AND DISPENSING |
| | SYSTEM |
| | A SEPARATE PERMIT IS REQUIRED FOR NEW FUEL TANKS AND |
| | DISPENSING SYSTEM |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19020380 2970 N MILITARY TRAIL |