2019-03-28 16:00:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 NFPA 30A
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
  
 PART A: BASED UPON REVIEW OF PLAN SHEETS C8, C8.1,
 C8.6, SD1, P001, POO2, P100, P110, P120, P410, P430,
 P431 AND A141, THE FOLLOWING COMMENTS APPLY.
  
 SEPARATE PERMITS ARE REQUIRED FOR GREASE INTERCEPTOR
 AND WATER SERVICE BACKFLOW PREVENTER.
  
 PER WPB FBC 107.2.1:
 1. PROVIDE CALCULATIONS FOR SIZING OF THE OIL/GREASE
 INTERCEPTOR.
 2. PROVIDE SAMPLE POINT IN GREASE INTERCEPTOR EFFLUENT
 AS REQUIRED BY CITY OF WEST PALM BEACH PUBLIC UTILITIES
 DEPARTMENT. SEE STANDARD DETAIL GS-7 PROVIDED BY PUBLIC
 UTILITIES DEPARTMENT. CONTACT JEFF ODOMS AT
 561-822-2172 FOR COPY OF STANDARD OR WITH ANY OTHER
 RELATED QUESTIONS.
 3. PROVIDE DETAIL FOR INDIRECT WASTE CONNECTIONS TO
 EQUIPMENT ITEMS #4119 AND #4124 SHOWING COMPLIANCE WITH
 FBC PL 802.2.
 4. PLAN P410: PLEASE PROVIDE REFERENCE TO P110, SHEET
 KEY NOTE 14 FOR THE FS-2 DISCHARGING THROUGH THE 2?
 FIXTURE DRAIN CONNECTING AT THE UPSTREAM (SOUTH) END OF
 THE GREASY WASTE.
 5. CLARIFY P430/DETAIL 3 THAT THE THREE COMPARTMENT
 SINK IS NOT FOR FOOD PREP OR INDEPENDENTLY DRAIN EACH
 COMPARTMENT TO THE FLOOR SINK WITH AN AIR GAP IN
 ACCORDANCE WITH FBC PL 802.1.1.
 6. PLAN P410: SANITARY RISER; MEN?S AND WOMEN?S TOILET
 ROOM FD-1 FIXTURE DRAINS CONNECT TO VENT BELOW THE TRAP
 WEIR (S-TRAP, PROHIBITED PER FBC 1002.3). VENT IN
 ACCORDANCE WITH PROVISIONS OF FBC PL CHAPTER 9.
 7. NOTES AND DETAILS CONCERNING THE TRAP PRIMERS ON
 P431/DETAIL 1, P110/ KEYNOTE 1 AND P100/PLUMBING
 FIXTURE SCHEDULE ALL DISAGREE ON THE TYPE AND/OR MODEL
 TRAP PRIMER. PLEASE CLARIFY.
 8. P431/DETAIL 6: WHAT IS THE PURPOSE OF THE FS-1 AT
 THE RIGHT HAND (SOUTH) SIDE OIF THE DETAIL. THIS FS-1
 IS ALSO SHOWN ON P110 AND P410.
 9. P110/KEYNOTE 15; PROVIDE DETAIL FOR PATIO ROOF DRAIN
 BODY, CONNECTION TO DOWNSPOUT AND TERMINATION OF
 DOWNSPOUT. INCLUDE REQUIRED HORIZONTAL AND VERTICAL
 SUPPORTS OF THE SAME.
 10. P410: A WATER BOOSTER IS NOTED ON THE WATER RISER
 DIAGRAM. PLEASE NOTE ON P002 (EQUIPMENT ITEM 5022) AND
 PROVIDE A KEYNOTE ON P120 INDICATING MCCANN?S 2 GALLON
 WATER BOOSTER W/ASSE 1022 BACKFLOW PREVENTER.
 11. P430/DETAIL 6 NON FREEZE ROOF HYDRANT: PLEASE
 SPECIFY A MANUFACTURER/MODEL NUMBER WHICH INCLUDES A
 VACUUM BREAKER.
 12. C8 AND SD1/DETAIL 12: SD1/DETAIL 12 CREATES A
 HAZARDOUS CONDITION. IN ACCORDANCE WITH FBC 608.7,
 608.8.1 AND 608.8.2, PROVIDE A BACKFLOW PREVENTER FOR
 THE DEDICATED SUPPLY, SIGNAGE AT THE HYDRANTS AND
 EXPOSED PIPING SHALL BE COLOR PURPLE AND LABELED.
 13. IDENTIFY ON P120 FLOOR PLAN AND P410 WATER RISER
 DIAGRAM ITEM 3016/RINSE-O-MATIC.
 14. IDENTIFY ON P120 FLOOR PLAN ITEM 4096/GLYCOL
 CHILLER
 15. IDENTIFY 2014/HOSE REEL LOCATED ADJACENT TO
 3008/CAPPUCCINO ON P120 FLOOR PLAN.
 16. RE: 2008/WATER FILTER; COULD NOT FIND INFO ON MODEL
 NUMBER EV9437-31. DID YOU MEAN EV9437-21? PLEASE
 CLARIFY.
 17. PROVIDE MANUFACTURER?S DATA SHEETS FOR ALL
 SPECIALTY EQUIPMENT REQUIRING PLUMBING CONNECTIONS (SEE
 PLAN SHEETS P002 AND A141)
 18. PROVIDE SEPARATE BACK FLOW PREVENTION DEVICES,
 LISTING THE APPLICABLE ASSE STANDARD REQUIREMENT, FOR
 EACH OF THE FOLLOWING;
 A. 4096/GLYCOL CHILLER
 B. 4013/ICE MAKER
 C. 4011/ICE MAKER
 E. 3017/COFFEE MACHINE
 F. 3016/RINSE-O-MATIC
 G. 3014/FCB VIPER
 H. 3011/COMBI OVEN STEAMER-EACH HOSE BIBB
 I. 3008/CAPPUCCINO DISPENSER
 J. 3007/GRANITA MACHINE
 K. 3002/TEA BREWER
 L. 2020/BEAN TO CUP WATER FILTER
 M. 2014/HOSE REEL
 N. RE: P430/DETAIL 6
 1) 2008/WATER FILTER PRIMARY
 2) 2008/WATER FILTER SECONDARY TO ICE MAKERS, COFFEE
 MAKERS, ETC.
 3) 2008/WATER FILTER BYPASS
  
 PART B: BASED UPON REVIEW OF PLAN SHEETS SURVEY 1 OF 1,
 C8, T1.0, T1.1, T1.2, T1.3, T2.0, T3.0, T4.0 AND T5.0,
 THE FOLLOWING COMMENTS APPLY.
  
 A SEPARATE PERMIT IS REQUIRED FOR REMOVAL AND
 DISPOSITION OF EXISTING FUEL TANKS AND DISPENSING
 SYSTEM
 A SEPARATE PERMIT IS REQUIRED FOR NEW FUEL TANKS AND
 DISPENSING SYSTEM
  
 PER WPB FBC 107.2.1:
 1. PROVIDE COPY OF PALM BEACH COUNTY OF ENVIRONMENTAL
 RESOURCES MANAGEMENT PERMIT
 2. PROVIDE MANUFACTURER?S DATA SHEETS FOR EACH FUEL
 TANK, DEAD MAN, TIE DOWN STRAPS, ANCHORING DETAILS AND
 ACCESSORIES.
 3. PROVIDE MANUFACTURER?S DATA SHEETS FOR TRANSITION
 SUMPS AND ACCESSORIES.
 4. PROVIDE MANUFACTURER?S DATA SHEETS FOR FUEL
 DISPENSERS AND ACCESSORIES.
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19020380 2970 N MILITARY TRAIL
  
  
  
  
  