2019-04-01 16:21:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SERVICE SHOWS ONE KIRK KEYED BREAKER WHICH WILL BE
 THE OTHER ONE?
  
 2) 1200 AMPERE MAIN NEEDS TO MEET THE REQUIREMENTS OF
 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE
 ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT
 BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL
 APPLY.
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE
 AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE
 INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S).
 (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE
 FOLLOWING
 OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED:
 (1) ZONE-SELECTIVE INTERLOCKING
 (2) DIFFERENTIAL RELAYING
 (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL
 STATUS
 INDICATOR
 (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM
 (5) AN APPROVED EQUIVALENT MEANS
  
 3) AIC RATING, NEED TO SHOW CALCULATION ON HOW IT WAS
 ACHIEVED.
  
 110.24 AVAILABLE FAULT CURRENT
 ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING
 UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
 MAXIMUM
 AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL
 INCLUDE THE DATE
 THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF
 SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
  
 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT
 CURRENT RATINGS, AND OTHER CHARACTERISTICS
 THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL
 IMPEDANCE, THE
 EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS, AND OTHER
 CHARACTERISTICS
 OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND
 COORDINATED
 TO PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR
 A FAULT TO DO
 SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT
 OF THE
 CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE EITHER
 BETWEEN TWO OR
 MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY CIRCUIT
 CONDUCTOR
 AND THE EQUIPMENT GROUNDING CONDUCTOR(S) PERMITTED IN
 250.118.
 LISTED EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR
 LISTING SHALL
 BE CONSIDERED TO MEET THE REQUIREMENTS OF THIS SECTION.