| 2019-04-01 16:21:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) SERVICE SHOWS ONE KIRK KEYED BREAKER WHICH WILL BE |
| | THE OTHER ONE? |
| | |
| | 2) 1200 AMPERE MAIN NEEDS TO MEET THE REQUIREMENTS OF |
| | 240.87 |
| | |
| | 240.87 ARC ENERGY REDUCTION |
| | WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR |
| | WHICH THE |
| | ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT |
| | BREAKER IS RATED |
| | OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND |
| | (B) SHALL |
| | APPLY. |
| | (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO |
| | THOSE |
| | AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE |
| | INSTALLATION |
| | AS TO THE LOCATION OF THE CIRCUIT BREAKER(S). |
| | (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE |
| | FOLLOWING |
| | OR APPROVED EQUIVALENT MEANS SH ALL BE PROVIDED: |
| | (1) ZONE-SELECTIVE INTERLOCKING |
| | (2) DIFFERENTIAL RELAYING |
| | (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL |
| | STATUS |
| | INDICATOR |
| | (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM |
| | (5) AN APPROVED EQUIVALENT MEANS |
| | |
| | 3) AIC RATING, NEED TO SHOW CALCULATION ON HOW IT WAS |
| | ACHIEVED. |
| | |
| | 110.24 AVAILABLE FAULT CURRENT |
| | ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN |
| | DWELLING |
| | UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE |
| | MAXIMUM |
| | AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL |
| | INCLUDE THE DATE |
| | THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF |
| | SUFFICIENT |
| | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. |
| | |
| | 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT |
| | CURRENT RATINGS, AND OTHER CHARACTERISTICS |
| | THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL |
| | IMPEDANCE, THE |
| | EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS, AND OTHER |
| | CHARACTERISTICS |
| | OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND |
| | COORDINATED |
| | TO PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR |
| | A FAULT TO DO |
| | SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT |
| | OF THE |
| | CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE EITHER |
| | BETWEEN TWO OR |
| | MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY CIRCUIT |
| | CONDUCTOR |
| | AND THE EQUIPMENT GROUNDING CONDUCTOR(S) PERMITTED IN |
| | 250.118. |
| | LISTED EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR |
| | LISTING SHALL |
| | BE CONSIDERED TO MEET THE REQUIREMENTS OF THIS SECTION. |