Plan Review Notes
Plan Review Notes For Permit 19020380
Permit Number 19020380
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-06 10:34:492017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020380
 ADD: 2970 N MILITARY TRAIL / CONVENIENCE STORE /
 ANNEXATION IN PROGRESS
 CONT: TBD / TO BE DETERMINED
 TEL: ???????????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. MARCH 5/ 2019
 ACTION: DENIED
  
 1) THIS PERMIT APPLICATION FOR ACONVENIENCE STORE &
 DUMPSTER ENCLOSURE IS FOR A PROPERTY BEING ANNEXED INTO
 THE CITY OF WEST PALM BEACH. NO PERMIT CAN BE ISSUED
 UNTIL THIS PROCESS IS COMPLETE. THE OTHER ISSUE IS A
 CONTRACTOR WILL NEED TO SIGN ON AS THE CONTRACTOR OF
 RECORD FOR THE REMOVAL OF THIS BUILDING. 2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.1
 REQUIRED.
  
 2) STRUCTURAL CALCULATIONS BY JOHN N. KABAK P. E.
 APPEARS TO BE A SCANNED IN PAPER DOCUMENT, NO
 ELECTRONIC SIGNATURE.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) ENERGY CALCULATIONS BY COM-CHECK ON THE 2ND PAGE THE
 ARCHITECTS SIGNATURE AND SEAL (MARK SALOPEK) IS NOT AN
 ELECTRONIC SIGNATURE.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 4) THE SURFACE WATER MANAGEMENT REPORT DOES NOT STATE
 THAT THEY ARE AN ENGINEERING FIRM, NOR IS THERE A INDEX
 STATING OF WHAT PORTION A PARTICULAR ENGINEER WAS IN
 CONTROL OVER.
 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET.
  
 5) IT WOULD APPEAR THAT THE COMPLETE SET OF 134 SHEETS
 ENCOMPASSING THE SUBMITTED PLANS ARE EITHER COPIES, OR
 JUST NOT ELECTRONICALLY SIGNED AND SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 6A) PLEASE REMOVE THE SHEETS THAT ARE UNDER DIFFERENT
 PERMITS, DEMO SHEETS, DUMPSTER ENCLOSURE, CANOPY SHEETS
 AND THE UNDERGROUND TANKS AND ASSOCIATED PIPING AND
 ASSOCIATED PUMPS AND VENTING. PLEASE ALSO NOTE THAT AS
 OF THIS DATE NO PERMIT HAS BEEN APPLIED FOR THE
 UNDERGROUND TANKS. THIS PERMIT TO BE ISSUED MUST ALSO
 HAVE PALM BEACH COUNTY ERM APPROVAL.
  
 6B) PLEASE ALSO INCLUDE THE SEQUENCE OR SCHEDULING OF
 THE CANOPY FOUNDATION AND UNDERGROUND TANK INSTALLATION
 BECAUSE OF THE DEPTH OF THE TANKS UNDERGROUND AND THE
 CLOSENESS TO THE CANOPY FOUNDATIONS. SHOW HOW
 COMPLIANCE WITH SECTION EXCAVATION NEAR FOUNDATIONS
 WILL BE COMPLIED WITH.
 THIS IS CRUCIAL SINCE THERE MAYBE 2 DIFFERENT
 CONTRACTORS INVOLVED, A BUILDING OR GENERAL CONTRACTOR
 FOR THE CANOPY AND A POLLUTANT STORAGE SYSTEM
 CONTRACTOR FOR THE UNDERGROUND TANKS, AND UNDERGROUND
 PIPING ASSOCIATED WITH THIS INSTALLATION.
 2017 FBC-B 1803.5.7 EXCAVATION NEAR FOUNDATIONS. WHERE
 EXCAVATION WILL REDUCE SUPPORT FROM ANY FOUNDATION, A
 REGISTERED DESIGN PROFESSIONAL SHALL PREPARE AN
 ASSESSMENT OF THE STRUCTURE AS DETERMINED FROM
 EXAMINATION OF THE STRUCTURE, THE REVIEW OF AVAILABLE
 DESIGN DOCUMENTS AND, IF NECESSARY, EXCAVATION OF TEST
 PITS. THE REGISTERED DESIGN PROFESSIONAL SHALL
 DETERMINE THE REQUIREMENTS FOR UNDERPINNING AND
 PROTECTION AND PREPARE SITE-SPECIFIC PLANS, DETAILS AND
 SEQUENCE OF WORK FOR SUBMISSION. SUCH SUPPORT SHALL BE
 PROVIDED BY UNDERPINNING, SHEETING AND BRACING, OR BY
 OTHER MEANS ACCEPTABLE TO THE BUILDING OFFICIAL.
  
 7) SHEET 050A001 ACCESSIBILITY DETAILS ALL USE THE 2010
 ADA AS REFERENCE, PLEASE UPDATE THE PLANS TO THE 2017
 FLORIDA ACCESSIBILITY CODE WHICH IS BLESSED BY THE
 DEPARTMENT OF JUSTICE SINCE IT IS MORE RESTRICTIVE THAN
 THE 2010 ADA. 2017 FBC-ACCESSIBILITY CODE 101 PURPOSE.
  
 8) SHEET 050A001 ACCESSIBILITY DETAIL FIGURE 502.2 DOES
 NOT REFLECT THE STRIPPING DETAIL FOR THE CITY OF WEST
 PALM BEACH. THE 2017 ACCESSIBILITY CODE THE SECTION FOR
 MARKING 502.3.3 AND ADVISORY STATES THAT THE METHOD AND
 COLOR OF MARKING ARE NOT SPECIFIED BY THESE
 REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL
 LAWS OR REGULATIONS.
 PLEASE REFER TO THE WEST PALM BEACH MUNI CODE ARTICLE
 XV PARKING, 94-485 STALL PAINTING DETAILS.
  
 9) SHEET 050A001 ACCESSIBLE PARKING: NOTE F REFERS TO
 THE REQUIREMENT FOR SIGNAGE, PLEASE REFER TO FLORIDA
 STATUTE 553.5041 FOR ACCESSIBLE PARKING SIGN AND THE
 SIGN COLOR AND DESIGN APPROVED BY THE DEPARTMENT OF
 TRANSPORTATION (ACCESS. CODE 502.6.1.)
  
 10) SHEET 050A001 DETAIL 8. PLEASE REFER TO THE 2017
 FBC-ACCESSIBILITY CODE SECTION 904.5.1 SELF SERVING
 SHELVES AND DISPENSING DEVISES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL COMPLY WITH 308 OF
 THIS CODE. 308 IS REACH RANGES.
  
 11A) SHEET 050A001 DETAIL 8 PLEASE ACCESSIBLE SEATING
 TO MEET THE REQUIREMENT OF ACCESS. CODE 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK SURFACES
 INCLUDE WRITING SURFACES, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 11B) SHEET 052_A003 LIFE SAFETY PLAN. PLEASE SHOW
 COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE;
 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
 11C) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 11D) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 12) SHEET 050A001 DETAIL 10 TOILET / PLUMBING FIXTURES
 SHOWS CLEARANCES FOR WATER CLOSETS, PLEASE BE AWARE THE
 2017 FBC-ACCESSIBILITY CODE FOR NEW CONSTRUCTION DOES
 REQUIRE THE LAV TO BE IN THE SAME COMPARTMENT BUT NOT
 IN THE CLEAR FLOOR SPACE FOR THE WATER CLOSET, SEE
 FIGURE 604.8.1.6.
  
 13) PLEASE NOTE THE COVERSHEET 049_A000 STATES THE
 CONSTRUCTION TYPE FOR THIS BUILDING IS V-B AND
 UNSPRINKLERED. THE LIFE SAFETY SHEET DOES NOT PROVIDE
 THE SQUARE FOOTAGE OF THE WALK-IN COOLER. SHEET
 059_A120 IS THE DIMENSION SHEET SO CALIBRATING AND
 MEASURING THE INTERIOR OF THE WALK-IN COOLER IT IS
 APPROXIMATELY 920 SQ. FT. NOT INCLUDING THE FREEZER. IN
 THE 2017 FBC-B SECTION 2603.4.1.3 LIMITS THE SQUARE
 FOOTAGE OF THE COOLER/ FREEZERS TO 400 SQ. FEET
 (ACCUMULATIVE) IN NON-SPRINKLERED BUILDINGS.
 SECTION 2603.4.1.2 HAS 4 LIMITATIONS THAT HAVE TO BE
 MET, THE LAST ONE IS THE COOLER WOULD HAVE TO BE
 PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 903.3.1.1.
  
 14) SHEETS A410-A423 SHOW THE USE OF A FLUID APPLIED
 WEATHER BARRIER OVER 5/8 INCH DENSGLASS SHEATHING.
 PLEASE NOTE THERE IS NO DEFINITION OR REQUIREMENT FOR
 WEATHER BARRIER IN THE CODE, BUT THERE IS FOR A
 WATER-RESISTIVE BARRIER.
 DEFINITION: WATER-RESISTIVE BARRIER. A MATERIAL BEHIND
 AN EXTERIOR WALL COVERING THAT IS INTENDED TO RESIST
 LIQUID WATER THAT HAS PENETRATED BEHIND THE EXTERIOR
 COVERING FROM FURTHER INTRUDING INTO THE EXTERIOR WALL
 ASSEMBLY. PLEASE CHANGE YOUR TERMINOLOGY TO
 WATER-RESISTIVE BARRIER, MUST MEET THIS REQUIREMENT.
 THE 2017 FBC-B SECTION 1404.2 WATER-RESISTIVE BARRIER.
 1404.2 WATER-RESISTIVE BARRIER. NOT FEWER THAN ONE
 LAYER OF NO.15 ASPHALT FELT, COMPLYING WITH ASTM D226
 FOR TYPE 1 FELT OR OTHER APPROVED MATERIALS, SHALL BE
 ATTACHED TO THE STUDS OR SHEATHING, WITH FLASHING AS
 DESCRIBED IN SECTION 1405.4, IN SUCH A MANNER AS TO
 PROVIDE A CONTINUOUS WATER-RESISTIVE BARRIER BEHIND THE
 EXTERIOR WALL VENEER.
  
 SINCE THE FLUID APPLIED WEATHER BARRIER IS NOT AN
 APPROVED METHOD OF A WATER-RESISTIVE BARRIER THE
 DESIGNER OF RECORD CAN REVIEW FBC-B 1404.1. MATERIALS
 USED FOR THE CONSTRUCTION OF EXTERIOR WALLS SHALL
 COMPLY WITH THE PROVISIONS OF THIS SECTION. MATERIALS
 NOT PRESCRIBED HEREIN SHALL BE PERMITTED, PROVIDED THAT
 ANY SUCH ALTERNATIVE HAS BEEN APPROVED.
  
 THE DESIGNER OF RECORD CAN REQUEST IN WRITING TO THE
 BUILDING OFFICIAL ROBERT BROWN THIS TYPE OF
 WATER-RESISTIVE BARRIER BE ACCEPTED AND APPROVED UNDER:
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 104.11 ALTERNATIVE MATERIALS, DESIGN AND
 METHODS OF CONSTRUCTION AND EQUIPMENT. THE PROVISIONS
 OF THIS CODE ARE NOT INTENDED TO PREVENT THE
 INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED
 BY THIS CODE, PROVIDED THAT ANY SUCH ALTERNATIVE HAS
 BEEN APPROVED. AN ALTERNATIVE MATERIAL, DESIGN OR
 METHOD OF CONSTRUCTION SHALL BE APPROVED WHERE THE
 BUILDING OFFICIAL FINDS THAT THE PROPOSED DESIGN IS
 SATISFACTORY AND COMPLIES WITH THE INTENT OF THE
 PROVISIONS OF THIS CODE, AND THAT THE MATERIAL, METHOD
 OR WORK OFFERED IS, FOR THE PURPOSE INTENDED, AT LEAST
 THE EQUIVALENT OF THAT PRESCRIBED IN THIS CODE IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY.
 WHEN ALTERNATE LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO PERFORMANCE-BASED FIRE
 PROTECTION ANALYSIS AND DESIGN OF BUILDINGS, OR OTHER
 METHODS APPROVED BY THE BUILDING OFFICIAL MAY BE USED.
 THE BUILDING OFFICIAL SHALL REQUIRE THAT SUFFICIENT
 EVIDENCE OR PROOF BE SUBMITTED TO SUBSTANTIATE ANY
 CLAIM MADE REGARDING THE ALTERNATIVE.
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR
 ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE,
 SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED
 SOURCES.
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS OF THIS CODE, OR
 EVIDENCE THAT A MATERIAL OR METHOD DOES NOT CONFORM TO
 THE REQUIREMENTS OF THIS CODE, OR IN ORDER TO
 SUBSTANTIATE CLAIMS FOR ALTERNATIVE MATERIALS OR
 METHODS, THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY
 TO REQUIRE TESTS AS EVIDENCE OF COMPLIANCE TO BE MADE
 AT NO EXPENSE TO THE JURISDICTION. TEST METHODS SHALL
 BE AS SPECIFIED IN THIS CODE OR BY OTHER RECOGNIZED
 TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED AND
 ACCEPTED TEST METHODS, THE BUILDING OFFICIAL SHALL
 APPROVE THE TESTING PROCEDURES. TESTS SHALL BE
 PERFORMED BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS
 SHALL BE RETAINED BY THE BUILDING OFFICIAL FOR THE
 PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
 15) SHEET 057_A110 NOTE 30 INDICATES THE PLACEMENT OF A
 PROPANE CAGE WITH CYLINDERS ON THE EXTERIOR OF THE
 BUILDING.
 PLEASE PROVIDE THE AMOUNT OF 20 LB. PROPANE CYLINDERS
 THAT CAN BE CONTAINED IN THIS CAGE AND COMPLIANCE WITH
 THE:
 2017 FBC-B F] 414.6 OUTDOOR STORAGE, DISPENSING AND
 USE. THE OUTDOOR STORAGE, DISPENSING AND USE OF
 HAZARDOUS MATERIALS SHALL BE IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE.
  
 F] 414.6.1.2 SEPARATION DISTANCE. THE DISTANCE FROM THE
 STRUCTURE TO BUILDINGS, LOT LINES, PUBLIC WAYS OR MEANS
 OF EGRESS TO A PUBLIC WAY SHALL BE NOT LESS THAN THE
 DISTANCE REQUIRED FOR AN OUTSIDE HAZARDOUS MATERIAL
 STORAGE OR USE AREA WITHOUT WEATHER PROTECTION.
  
 [F] 414.6.1.3 NONCOMBUSTIBLE CONSTRUCTION. THE OVERHEAD
 STRUCTURE SHALL BE OF APPROVED NONCOMBUSTIBLE
 CONSTRUCTION WITH A MAXIMUM AREA OF 1,500 SQUARE FEET.
  
 16) SHEET 092_S000 INDICATES THE WIND DESIGN AND THE
 UPPER RIGHT CORNER OF THE SHEET THE COMPONENTS &
 CLADDING PRESSURES IN (VULT 170 MPH) WHICH ARE REVIEWED
 AND CORRECT. PLEASE SUBMIT A COMPONENTS AND CLADDING
 TABLE IN VASD FOR THE EXPOSURE C SINCE ALL OF THE
 PRODUCT APPROVALS ARE IN VASD. THANK YOU FOR YOUR
 COOPERATION. 1609.3.1 WIND SPEED CONVERSION VULT TO
 VASD.
  
 17) THE COVERSHEET PROVIDES A LIST OF APPROVED PRODUCT
 APPROVALS, THIS LIST CAN BE DEFERRED SUBMITTALS, AFTER
 PERMIT ISSUANCE. PLEASE SEE LIST OF PRODUCTS THAT MAY
 OR MAY NOT BE ON YOUR APPROVED LIST.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, HARDI PLANK CMC PANELS AND AMC
 PANELS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, CURBS & ADAPTORS, ROOF TOP
 VENTILATORS & EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 18) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 19) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 20) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 21) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 22) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 23) PLEASE BE ADVISED UNDER THE 2017 FBC-B SECTIONS
 1704 AND 1705 ARE RESERVED. FOR THE STRUCTURAL/
 BUILDING PORTION FOR INSPECTIONS THE CITY BUILDING
 INSPECTORS WILL COMPLETE ALL SCHEDULED INSPECTIONS WITH
 THE EXCEPTION OF WELDED AND BOLTED CONNECTIONS WITH
 STRUCTURAL STEEL. A 3RD PARTY ENGINEER IS TO COMPLETE
 JOBSITE INSPECTIONS OF WELDED AND BOLTED CONNECTIONS
 AND CERTIFY WELD PROCEDURE SPECIFICATIONS & WELDER
 OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
  
 24) SHEET 107_M300 DETAIL 8 INDICATES HOW THE ROOF TOP
 CONDENSER IS TO BE MOUNTED TO THE EQUIPMENT RACK BUT
 NOT TO THE ROOF DECK. SHEET 100_S432 DETAIL 10 DOES
 INDICATE ANCHORAGE TO THE ROOF BUT NEITHER DETAIL SHOWS
 COMPLIANCE WITH THE 2017 FBC-B TABLE 1510.10 CLEARANCE
 BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
  
 25) ADDITIONAL INFORMATION IS REQUIRED? SHEET S200 THE
 ROOF FRAMING PLAN ON THE SIDE PATIO ROOF FRAMING THERE
 IS A SECTION DETAIL 3 & 4 / S433. DETAIL 4 OCCURS AT
 BOTH ENDS OF THE PATIO COVER ALLOWING THE BRICK VENEER
 WALL TO CONTINUE BEHIND THE ROOF FRAMING. DETAIL # 3
 THE CENTER PORTION OF THE PATIO ROOF DECK IT WOULD
 APPEAR THE VENEER BRICK WALL STOPS BENEATH THE BOTTOM
 OF THE STRUCTURAL STEEL FRAMING, THE ROOF METAL DECK
 CONTINUES BACK INSIDE THE STEEL INFILL WALL AND THE
 BRICK WORK SITS ON TOP OF THE ROOF METAL DECK WITHOUT
 ANY STRUCTURAL SUPPORT? PLEASE CLARIFY THIS DETAIL,
 THANK YOU. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. THE ARCHITECTURAL SHEET 080_A431 DETAIL 11
 MATCHES THE STRUCTURAL DETAILS FOR BOTH ENDS, DETAIL 1
 ON SHEET 078_A423 SHOW THE ROOF DECK STOPPING ON THE
 EXTERIOR SIDE OF THE BRICK, NOT CLEAR WHERE THE BRICK
 STOPS AND STARTS IN REGARDS TO THE STRUCTURAL DECK
 MEMBERS?
  
 26) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 27) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  