Plan Review Notes
Plan Review Notes For Permit 19020378
Permit Number 19020378
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-05 08:14:522017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020378
 ADD: 2970 N MILITARY TRAIL / CANOPY/ ANNEXATION IN
 PROGRESS
 CONT: TBD / TO BE DETERMINED
 TEL: ???????????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. MARCH 5/ 2019
 ACTION: DENIED
  
 1) THIS PERMIT APPLICATION FOR A CANOPY IS FOR PROPERTY
 BEING ANNEXED INTO THE CITY OF WEST PALM BEACH. NO
 PERMIT CAN BE ISSUED UNTIL THIS PROCESS IS COMPLETE.
 THE OTHER ISSUE IS A CONTRACTOR WILL NEED TO SIGN ON AS
 THE CONTRACTOR OF RECORD FOR THE REMOVAL OF THIS
 BUILDING. 2017 FLORIDA BUILDING CODE W 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 105.1 REQUIRED.
  
 2) THE SOILS REPORT BY GFA INTERNATIONAL FOUND THE
 GROUND WATER TABLE APPROXIMATELY 3.08? TO 4.5 ? BELOW
 GRADE. THE BOTTOM OF THE CANOPY IS 6.75? BELOW GRADE.
 THE REPORT DOES INDICATE UNDER THE HEADING OF 3.2.2
 SITE PREPARATION COMMENT # 8 DOES INDICATE DEWATERING
 OR REMOVAL TEMPORARY PERCHED WATER MAY NEED TO OCCUR.
 THE SUBMITTED SOILS REPORT DOES NOT ADDRESS THE NEEDED
 DEWATERING FOR THE CANOPY FOOTINGS NOR THE EXCAVATION
 REQUIRED FOR THE 3 UNDERGROUND STORAGE TANKS. PLEASE
 PROVIDE A DEWATERING PLAN FOR BOTH THE CANOPY
 FOUNDATION AS WELL AS FOR THE 3 UNDERGROUND STORAGE
 TANKS. 1803.5.4. GROUND WATER TABLE.
  
 3) PLEASE ALSO INCLUDE THE SEQUENCE OR SCHEDULING OF
 THE CANOPY FOUNDATION AND UNDERGROUND TANK INSTALLATION
 BECAUSE OF THE DEPTH OF THE TANKS UNDERGROUND AND THE
 CLOSENESS TO THE CANOPY FOUNDATIONS. SHOW HOW
 COMPLIANCE WITH SECTION EXCAVATION NEAR FOUNDATIONS
 WILL BE COMPLIED WITH.
 THIS IS CRUCIAL SINCE THERE MAYBE 2 DIFFERENT
 CONTRACTORS INVOLVED, A BUILDING OR GENERAL CONTRACTOR
 FOR THE CANOPY AND A POLLUTANT STORAGE SYSTEM
 CONTRACTOR FOR THE UNDERGROUND TANKS, AND UNDERGROUND
 PIPING ASSOCIATED WITH THIS INSTALLATION.
  
 2017 FBC-B 1803.5.7 EXCAVATION NEAR FOUNDATIONS. WHERE
 EXCAVATION WILL REDUCE SUPPORT FROM ANY FOUNDATION, A
 REGISTERED DESIGN PROFESSIONAL SHALL PREPARE AN
 ASSESSMENT OF THE STRUCTURE AS DETERMINED FROM
 EXAMINATION OF THE STRUCTURE, THE REVIEW OF AVAILABLE
 DESIGN DOCUMENTS AND, IF NECESSARY, EXCAVATION OF TEST
 PITS. THE REGISTERED DESIGN PROFESSIONAL SHALL
 DETERMINE THE REQUIREMENTS FOR UNDERPINNING AND
 PROTECTION AND PREPARE SITE-SPECIFIC PLANS, DETAILS AND
 SEQUENCE OF WORK FOR SUBMISSION. SUCH SUPPORT SHALL BE
 PROVIDED BY UNDERPINNING, SHEETING AND BRACING, OR BY
 OTHER MEANS ACCEPTABLE TO THE BUILDING OFFICIAL.
  
 4) PLEASE NOTE NONE OF THE SITE PLANS, SURVEY, CANOPY
 FOUNDATION, ROOF PLAN, CANOPY MISC. PLAN NOR THE FUEL
 CANOPY PLAN AND ELEVATIONS ARE ELECTRONICALLY SIGNED
 AND SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 5A) PLEASE NOTE ON THE FOUNDATION PLAN 004_CANOPY
 FOUNDATION PLAN UNDER THE FIGURE C-1 THERE IS A COLUMN
 SCHEDULE C-1 THROUGH C-8 THAT IS BLANK IT WOULD APPEAR
 IT NEEDS TO BE FILED IN.107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5B) PLEASE NOTE ON THE FOUNDATION PLAN 004_CANOPY
 FOUNDATION PLAN UNDER APPROVALS FOR THE CANOPY IT WOULD
 APPEAR THAT A DESIGN PROFESSIONAL IS TO APPROVE THESE
 DRAWINGS WITH AS SUBMITTED OR APPROVED WITH NOTED
 CHANGES AND APPROVED BY ??????? AND DATED.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) THE CANOPY PLAN AND CANOPY MISC. DETAIL PLAN SHOWS
 MISC. CANOPY ROOFING MATERIALS (CANOPY METAL DECKING)
 AND ANCHORS, PLEASE SUPPLY PRODUCT APPROVALS FOR THESE
 SYSTEMS.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 7) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) SHEET 004_CANOPY FOUNDATION PLAN HAS A HEADING FOR
 GENERAL NOTES AND WITHIN THESE NOTES THERE IS THE
 INFORMATION FOR THE WIND DESIGN CRITERIA, AND THE
 BUILDING IS DESIGNED AS A OPEN BUILDING, BUT THE
 MISSING INFORMATION WOULD BE THE POSITIVE/ NEGATIVE
 PRESSURES FOR ROOF ZONES 1, 2 & 3.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS.
  
 10) INFORMATIONAL ONLY, THE CANOPY WILL NOT NEED TO GO
 FOR IMPACT FEE REVIEW, BUT THE GAS/ DIESEL PUMPS WILL
 NEED TO GO FOR IMPACT FEE REVIEW, POINT OF SALE.
  
 11) WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  