Plan Review Notes
Plan Review Notes For Permit 19020377
Permit Number 19020377
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-02-11 09:08:07PERMIT #19020377
 FIRE REVIEW COMMENTS
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 SUE ELLEN CALDERON
 ASST, FIRE MARSHAL
 WPBFR