| 2019-03-12 18:22:17 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020375 |
| | 3/12/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW OFFICE AC SYSTEM- SECTION C403.2.1 FBC EC. |
| | |
| | 2) SUBMIT ENERGY CALCULATIONS FOR THE NEW CONDITIONED |
| | ENCLOSED SPACE- SECTION C503.2 FBC EC. REFER TO SECTION |
| | C402.2.2: INSULATION INSTALLED ON THE SUSPENDED CEILING |
| | SHALL BNOT BE CONSIDERED PART OF THE MINIMUM THERMAL |
| | RESISTANCE OF THE ROOF INSULATION. |
| | |
| | 3) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| | FOR THE ROOF STAND AND LOUVER. |
| | |
| | 4) M-1: PROVIDE AN AUTOMATICALLY CONTROLLED SHUTOFF |
| | DAMPER FOR THE O/A INTAKE DUCT- SECTION C403.2.4.3 |
| | FBC-17 EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |