| 2019-02-27 08:01:36 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020375 |
| | ADD: 5786 PREMIER PARK DR. |
| | CONT: DUKE INDIANA CONSTRUCTION |
| | TEL: 954-453-5660 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 27/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) THE ORIGINAL PERMIT FOR THIS TENANT SPACE 10040216 |
| | AND THE APPLIED FOR PERMIT / PLANS INDICATE THAT THIS |
| | IS A FIRE SPRINKLERED BUILDING. LESS THAN 50 HEADS A |
| | FIRE SPRINKLER CONTRACTOR CAN DESIGN THE ADDITIONAL |
| | HEADS IN AN EXISTING FIRE SPRINKLER SYSTEM. A |
| | CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED |
| | UNDER SECTION 633.521, FLORIDA STATUTE MAY DESIGN A |
| | FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY |
| | DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 2) NOTICE: SHEET A2.1 DOES INDICATE THERE WILL BE |
| | FUTURE RACK STORAGE UNDER A SEPARATE PERMIT. NOTING |
| | THAT RACK STORAGE IS NOT PART OF THIS PERMIT. |
| | |
| | 3) SHEET A-2 DOES INDICATE THE EXTERIOR CONCRETE WALL |
| | WILL BE CUT AND SEE SHEET S-1. PLEASE ALSO REVIEW SHEET |
| | M-1, THE PLAN SHOWS A SECOND 12 X 12 INCH PENETRATION |
| | OF THE EXTERIOR WALL FOR INTAKE OF OUTSIDE AIR. SHEET |
| | S-1 DOES NOT INDICATE THE 2ND PENETRATION AND WILL NEED |
| | TO UPDATE THE PLANS. 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED. PLEASE ALSO INCLUDE THE PRESSURES FOR THE |
| | INTAKE LOUVER. |
| | |
| | 4A) PLEASE PROVIDE COMPLIANCE WITH: 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | (C) WALL LOUVERS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) SHEETS E-1 & M-1 BOTH SHOW A NEW ROOF TOP A/C |
| | COMPRESSOR, SHEET M2 HAS CODE LANGUAGE FROM THE 2007 |
| | FBC-B ABOUT ROOF MOUNTED A/C UNITS AND THE MINIMUM |
| | HEIGHT OF THE STANDS LISTING TABLE 1509.7. PLEASE |
| | UPDATE THE PLANS TO THE 2017 FBC-B TABLE 1510.10. IF |
| | THE PIPE STAND DETAIL FOUND ON M2 IS TO BE USED THEN |
| | PLEASE PROVIDE THE WELD INFORMATION MISSING FROM THE |
| | PLANS AS WELL TO WHAT WIND SPEED DESIGN WAS USED FOR |
| | THE ANCHORING OF THE ROOF TOP STAND TO THE ROOF FRAMING |
| | MEMBERS AND THE ROOF TOP UNIT TO THE STAND. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2) QUALIFICATIONS OF WELDING PERSONAL |
| | |
| | 6) THE ARCHITECTURAL SHEETS DOES NOT SHOW A ROOF PLAN |
| | BUT THE MECHANICAL SHEET M-1 DOES SHOW THE NEW ROOF TOP |
| | COMPRESSOR. THE PLANS DO NOT INDICATE HOW YOU ARE TO |
| | GAIN ACCESS ONTO THE ROOF. SHOW COMPLIANCE WITH: |
| | 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS |
| | OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR |
| | THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO |
| | CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO |
| | ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR |
| | EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS |
| | SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER |
| | THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS |
| | HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL |
| | NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS |
| | INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL |
| | BE MEASURED TO THE TOP OF THE PARAPET WALL. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |