| 2019-02-11 18:17:10 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL |
| | FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE |
| | UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT |
| | OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING |
| | IS REQUIRED: |
| | |
| | A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC. |
| | 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC. |
| | 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC. R301.1 |
| | FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT |
| | CAN NOT BE USED. |
| | |
| | B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION |
| | 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM |
| | FRSA/TRI APRIL 2012 (04-12), APPENDIX A, TABLE 1. |
| | CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING. |
| | |
| | 2- CLEARLY IDENTIFY ON PRODUCT APPROVALS THE ROOF TILE |
| | PROFILE AND PADDY SIZE AS REQUIRED BY CITY POLICY FOR |
| | ALL ROOFING PERMITS. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WAS UPDATED TO $327,792. THE |
| | PERMIT FEE BALANCE IS $645.44. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |