Plan Review Notes
Plan Review Notes For Permit 19020363
Permit Number 19020363
Review Stop P
Sequence Number 2
Notes
Date Text
2019-08-06 15:00:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2NDT REVIEW
 PLUMBING COMMEMTS: DENIED
 1. UPON REVIEW OF THE PLANS UNDER PERMIT #97011131 AND
 19030705, THE FOLLOWING SHALL APPLY:
  
 A. PER WPB FBC 107.2.1, PROVIDE ADDITIONAL
 CLARIFICATION ON PLAN SHEET A1; CLOUD EACH
 NON-PERMITTED RECONFIGURATION AND ADDITION. CLARIFY
 BATH AS BUILT AS ADDED BATH. PROVIDE PLAN SHOWING THE
 EXISTING KITCHEN, LAUNDRY AND BATH CONFIGURATION AND
 LOCATIONS AT THE TIME OF THE ISSUANCE OF PERMIT
 #97011131. SEE PERMIT #97011131 PLAN SHEETS 2 AND 3.
 B. PER WPB FBC 107.2.1, THE GAS TANKLESS WATER HEATER
 SHALL BE SHOWN AND IDENTIFIED ON PLAN SHEET A1.
 C. SEE PLUMBING NOTES ON PLAN SHEET A2; PER WPB FBC
 107.2.1, THE PLUMBING SHALL COMPLY WITH FLORIDA
 RESIDENTIAL BUILDING CODE 2017.
 D. SEE PLUMBING PIPING ON PLAN SHEET A2; PER FBC RES
 P3104.3 AND P3104.4, DRY VENT SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND RISE
 VERTICALLY TO NOT LESS THAN 6? ABOVE THE FLOOD LEVEL
 RIM OF THE HIGHEST FIXTURE BEING VENTED.
 E. IS THE NEW ADDITION TO BE BUILT OVER THE EXISTING
 SANITARY SEWER/BUILDING DRAIN? SHOW LOCATION OF
 EXISTING SANITARY SEWER/BUILDING DRAIN AND WHERE ADDED
 BATH WILL CONNECT INTO THE SAME.
  
 2. AS A PROVISO TO AN APPROVED PERMIT, A VIDEO OF THE
 UNDERSLAB PIPING SHALL BE MADE AND PRESENTED TO THE
 PLUMBING INSPECTOR AT THE FIRST PLUMBING INSPECTION,
 WHICH SHALL BE REVIEWED BY THE CHIEF PLUMBING INSPECTOR
 FOR CODE COMPLIANCE.
 3. SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19020363 936 UPLAND RD
  