| 2019-08-06 15:00:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 96= STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2NDT REVIEW |
| | PLUMBING COMMEMTS: DENIED |
| | 1. UPON REVIEW OF THE PLANS UNDER PERMIT #97011131 AND |
| | 19030705, THE FOLLOWING SHALL APPLY: |
| | |
| | A. PER WPB FBC 107.2.1, PROVIDE ADDITIONAL |
| | CLARIFICATION ON PLAN SHEET A1; CLOUD EACH |
| | NON-PERMITTED RECONFIGURATION AND ADDITION. CLARIFY |
| | BATH AS BUILT AS ADDED BATH. PROVIDE PLAN SHOWING THE |
| | EXISTING KITCHEN, LAUNDRY AND BATH CONFIGURATION AND |
| | LOCATIONS AT THE TIME OF THE ISSUANCE OF PERMIT |
| | #97011131. SEE PERMIT #97011131 PLAN SHEETS 2 AND 3. |
| | B. PER WPB FBC 107.2.1, THE GAS TANKLESS WATER HEATER |
| | SHALL BE SHOWN AND IDENTIFIED ON PLAN SHEET A1. |
| | C. SEE PLUMBING NOTES ON PLAN SHEET A2; PER WPB FBC |
| | 107.2.1, THE PLUMBING SHALL COMPLY WITH FLORIDA |
| | RESIDENTIAL BUILDING CODE 2017. |
| | D. SEE PLUMBING PIPING ON PLAN SHEET A2; PER FBC RES |
| | P3104.3 AND P3104.4, DRY VENT SHALL CONNECT ABOVE THE |
| | CENTERLINE OF THE HORIZONTAL DRAIN PIPE AND RISE |
| | VERTICALLY TO NOT LESS THAN 6? ABOVE THE FLOOD LEVEL |
| | RIM OF THE HIGHEST FIXTURE BEING VENTED. |
| | E. IS THE NEW ADDITION TO BE BUILT OVER THE EXISTING |
| | SANITARY SEWER/BUILDING DRAIN? SHOW LOCATION OF |
| | EXISTING SANITARY SEWER/BUILDING DRAIN AND WHERE ADDED |
| | BATH WILL CONNECT INTO THE SAME. |
| | |
| | 2. AS A PROVISO TO AN APPROVED PERMIT, A VIDEO OF THE |
| | UNDERSLAB PIPING SHALL BE MADE AND PRESENTED TO THE |
| | PLUMBING INSPECTOR AT THE FIRST PLUMBING INSPECTION, |
| | WHICH SHALL BE REVIEWED BY THE CHIEF PLUMBING INSPECTOR |
| | FOR CODE COMPLIANCE. |
| | 3. SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |