| 2019-08-09 10:18:01 | MECHANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE ENERGY SUBMITTAL FOR ADDITION. |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| | (MANDATORY). |
| | |
| | 2. DESIGNER OF RECORD TO SIGN PLAN. |
| | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, |
| | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER |
| | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE |
| | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| | |
| | DIGITAL REVIEW |
| | |
| | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH |
| | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE |
| | NEXT REVIEW CYCLE REQUIRE REVIEW. |
| | |
| | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |