| Plan Review Notes For Permit 19020344 |
| Permit Number |
19020344 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-11 18:08:20 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVAL IS PENDING: | | | | | | FBC B 603.1 ITEM 2 EXCEPTION 2; SUBMIT THE FLAME SPREAD | | | INDEX SPECIFICATIONS (NOT MORE THAN 200) OR SUBMIT A | | | DIFFERENT PRODUCT THAT HAS BEEN TESTED FOR FLAME SPREAD | | | PER ASTM E 84 OR UL 723. |
|