Plan Review Notes
Plan Review Notes For Permit 19020342
Permit Number 19020342
Review Stop B
Sequence Number 2
Notes
Date Text
2019-06-05 08:09:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020342
 ADD: 1638 EMBASSY DR. SUITE: 301
 CONT: MJR CUSTOM HOMES
 TEL: 561-906-7574
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 6/5/2019
 ACTION: DENIED
  
 1) OK
  
 2) OK
  
 3) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 3A) UNDER WHAT EDITION OF THE FLORIDA BUILDING CODE WAS
 THE PLANS DESIGNED?
  
 3B) UNDER THE EXISTING BUILDING CODE UNDER WHICH METHOD
 WERE THE PLANS DEVELOPED?
  
 3C) 301.1 THE ALTERATION OF ALL EXISTING BUILDINGS
 SHALL COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
  
 3C)(1) 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
  
 3C)(2) 301.1.2 WORK AREA COMPLIANCE METHOD.
  
 3C)(3) 01.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 4) 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED.
  
 5) 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
  
 5) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS, THE WALL SEPARATING THE 2
 UNITS WHERE THE WORK IS COMMENCING ON THE
 SHOWER, THE PLANS ARE NOT CLEAR IF THE FIRE RATED
 DRYWALL IS BEING REMOVED?
  
 6) 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 PRE-ENGINEERED SYSTEMS. IS THE UNIT FIRE SPRINKLERED OR
 NOT?
  
 7) SINCE THE DEMO NOTE (1) INDICATES THE REMOVAL OF
 FLOOR TILE, THERE IS NO INFORMATION AS TO THE NEW FLOOR
 FINISH OR COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL (LVT) OR (LVP) AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 7A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 7B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 7C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 PLAN SPECIFIES "PROFLEX 90 OR EQUIVALENT". SPECIFY SLAB
 THICKNESS AND PROVIDE TEST REPORTS FOR THE PRODUCT
 PROPOSED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved