2019-02-25 08:03:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020342
 ADD: 1638 EMBASSY DR. SUITE: 301
 CONT: MJR CUSTOM HOMES
 TEL: 561-906-7574
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 25/ 2019
 ACTION: DENIED
  
 1A) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. FOR EACH TRADE THE CONTRACTOR RESPONSIBLE
 FOR THE DESIGN UNDER THE TRADE LICENSED IN MUST PRINT
 THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE
 THESE PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY
 WOULD HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 1B) PLEASE NOTE THERE ARE NOTES ON THE DEMO PLAN NOTED
 # 1 TO REMOVE ALL TILE THROUGHOUT THE HOUSE, PLEASE
 UPDATE THE PLANS THIS IS NOT A SINGLE FAMILY HOUSE.
 ALSO UNDER THE GENERAL NOTES THERE ARE REFERENCES TO
 SHUTTING OFF THE MAIN WATER VALVE TO THE HOUSE, AND
 DRIVEWAYS AND OTHER AREAS ARE TO BE PROTECTED. IT WOULD
 APPEAR WHOMEVER DESIGNED THIS PLAN IS A RESIDENTIAL
 DRAFTSMAN.
  
 2) PLEASE NOTE WITHIN THE ONE SHEET SUBMITTED THERE IS
 A INTERIOR DEMO FLOOR PLAN, NEW FLOOR PLAN FOR PLUMBING
 AND A ELECTRICAL FLOOR PLAN, THERE IS NO FLOOR PLAN FOR
 THE PROPOSED BUILDING PORTION OF THE PROJECT.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 3A) UNDER WHAT EDITION OF THE FLORIDA BUILDING CODE WAS
 THE PLANS DESIGNED?
  
 3B) UNDER THE EXISTING BUILDING CODE UNDER WHICH METHOD
 WERE THE PLANS DEVELOPED?
  
 3C) 301.1 THE ALTERATION OF ALL EXISTING BUILDINGS
 SHALL COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
  
 3C)(1) 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
  
 3C)(2) 301.1.2 WORK AREA COMPLIANCE METHOD.
  
 3C)(3) 01.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 4) 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED.
  
 5) 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
  
 5) 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS, THE WALL SEPARATING THE 2
 UNITS WHERE THE WORK IS COMMENCING ON THE
 SHOWER, THE PLANS ARE NOT CLEAR IF THE FIRE RATED
 DRYWALL IS BEING REMOVED?
  
 6) 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 PRE-ENGINEERED SYSTEMS. IS THE UNIT FIRE SPRINKLERED OR
 NOT?
  
 7) SINCE THE DEMO NOTE (1) INDICATES THE REMOVAL OF
 FLOOR TILE, THERE IS NO INFORMATION AS TO THE NEW FLOOR
 FINISH OR COMPLIANCE WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL (LVT) OR (LVP) AND WOOD
 FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT
 TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND
 MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE
 STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO
 DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 7A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 7B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 7C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER