| 2019-03-18 10:19:52 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | FAILED |
| | |
| | 1) THE APPLICATION IS UNDERVALUED. PROVIDE CONTRACT |
| | AMOUNT FOR ENTIRE SCOPE OF WORK OR VALUE FOR FULL |
| | SCOPE. |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) PROVIDE TEST REPORTS FROM A THIRD PARTY TESTING LAB |
| | FOR SOUND INSULATION PRODUCT TO DEMONSTRATE COMPLIANCE |
| | WITH THE SECTIONS BELOW. |
| | |
| | FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE |
| | W/FLAME SPREAD INDEX OF 200 OR LESS. |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |