| 2019-02-26 14:47:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | PLUMBING COMMENTS |
| | 1. PROVIDE A CODE COMPLIANT SANITARY RISER DIAGRAM |
| | SHOWING SIZED BUILDING DRAIN, FIXTURE DRAINS, TRAPS AND |
| | VENTS PER WPB FBC 107.3.5.3(12). |
| | 2. PROVIDE A NORTH ORIENTATION ON FLOOR PLANS PER WPB |
| | FBC 107.2.1. |
| | 3. THERE SEEMS TO BE A DISCREPENCY IN THE PATHROOM |
| | LAYOUT AS TO WHICH END HAS THE TOILET AND WHICH END HAS |
| | THE SHOWER. PLEASE CLARIFY. |
| | 4. PLEASE NOTE THAT IF YOUR NEW HOT WATER PIPING FROM |
| | THE EXISTING WATER HEATER EXCEEDS 50' THA,T PER FBC RES |
| | P2601.1 AND FBC PL 607.2 YOU WILL BE REQUIRED TO |
| | INSTALL A HOT WATER PUMPED RECIRC LINE OR HEAT TRACING |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |