2019-02-26 16:21:48BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLUMBING RISER PLAN SHOWS SHOWER AND TOILET
 COMPARTMENT IN REVERSE LOCATION THAN INDICATED ON
 FRAMING PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. EXHAUST FAN REQUIRED
 R303.3BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 3. R702.4.2 BACKER BOARDS.
 MATERIALS USED AS BACKERS FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALL PANELS IN SHOWER AREAS SHALL BE
 OF MATERIALS LISTED IN TABLE R702.4.2, AND INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS.
  
 4. R307.2 BATHTUB AND SHOWER SPACES.
 BATHTUB AND SHOWER FLOORS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS AND IN SHOWER COMPARTMENTS SHALL
 BE FINISHED WITH A NONABSORBENT SURFACE. SUCH WALL
 SURFACES SHALL EXTEND TO A HEIGHT OF NOT LESS THAN 6
 FEET (1829 MM) ABOVE THE FLOOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  