| 2019-03-06 10:41:44 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 1106 FBC-EXISTING BUILDING. AND SEC. R101.4.2 |
| | AND R101.5 FBC-ENERGY CONSERVATION. NOTE: COORDINATE |
| | WITH PLANS AND PRODUCT APPROVALS SUBMITTED TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2- PLANS NEED TO PROVIDE COMPLIANCE WITH THE HEATING |
| | REQUIREMENTS FOR NEW ROOM AS REQUIRED BY SEC. R303.10 |
| | FBC-RESIDENTIAL. (NOTE: MECHANICAL PERMIT MAY BE |
| | REQUIRED). |
| | |
| | 3- WALL SECTION 1/7 ON SHEET 7 OF 8: |
| | A) R-30 BATT INSULATION DOESN'T FIT ON A 2" X 8" ROOF |
| | RAFTERS. THE THICKNESS OF R-30 BATT INSULATION IS MORE |
| | OR LESS 9-1/2" THICK. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | B) SHOW COMPLIANCE WITH NEW ROOF CROSS VENTILATION AS |
| | REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. NOTE: |
| | INSULATION CAN NOT BLOCK THE CROSS VENTILATION. SEE |
| | SEC. R8016.3 FBC-RESIDENTIAL. COORDINATE WITH ITEM |
| | #3(A) ABOVE. |
| | |
| | C) CLARIFY IF THE NEW ROOM IS GOING TO BE AIR |
| | CONDITIONED. IF SO, THEN PROVIDE DETAILS AND |
| | SPECIFICATIONS FOR THE INSULATION BETWEEN THE EXISTING |
| | NON-A/C STORAGE ROOM AND THE NEW ROOM AS REQUIRED BY |
| | SEC. R103.2 FBC-RESIDENTIAL. ALSO, PROVIDE |
| | SPECIFICATIONS FOR INSULATION ON NEW EXTERIOR WOOD |
| | FRAMED WALL. |
| | |
| | D) SPECIFY RING SHANK NAILS FOR ROOF SHEATHING AS |
| | REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL. |
| | |
| | 4- SHEET 6 OF 8 IS MISSING THE ENGINEER' SEAL AS |
| | REQUIRED BY CHAPTER 471 F.S. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| | IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | B)FRENCH DOORS. PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PROVIDE 2 COPIES OF COMPLETE PRODUCT APPROVAL. |
| | ONLY ONE COPY WAS SUBMITTED. SEC. 107.1 CITY |
| | AMENDMENTS. |
| | |
| | C)SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE COPY |
| | WAS SUBMITTED. SEC. 107.1 CITY AMENDMENTS. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- PROVIDE COMPLETE WALL SECTION FOR NEW EXTERIOR WOOD |
| | FRAME WALL : SPECIFY ALL INTERIOR AND EXTERIOR FINISH |
| | MATERIALS. SPECIFY WALL SHEATHING TYPE AND FASTENERS. |
| | SPECIFY THE 2 REQUIRED WATER-RESISTIVE BARRIERS AS |
| | REQUIRED BY SE. R703.7.3 FBC-RESIDENTIAL. IF STUCCO |
| | FINISH, THEN SPECIFY STUCCO THICKNESS AS REQUIRED BY |
| | TABLE R702.1(1) FBC-RESIDENTIAL. |
| | |
| | 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH THE WIND |
| | RESISTANCE AS REQUIRED BY SEC. R703.1.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 9-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WAS UPDATED TO $32,964. THE |
| | PERMIT FEE BALANCE IS $722.20. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |