| Date |
Text |
| 2019-05-13 14:45:56 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | FBC R 401.3 (DRAINAGE) |
| | FBC 107.2.5 (SITE PLAN) |
| | FBC 110.9 (IMPACT OF CONSTRUCTION) |
| | |
| | RESPONSE: |
| | BASED ON DRAWINGS SUBMITTED WITH THE PROPOSED POOL AND |
| | BRICK PATIO, THE REAR PROPERTY REQUIRES MORE ATTENTION. |
| | PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN FOR |
| | ENTIRE LOT AS REQUIRED BY SEC. 110.9 CITY AMENDMENTS. |
| | |
| | 2- OK. |
| | |
| | 3- A) OK. |
| | |
| | B) THE TREAD DEPTH SHALL BE MEASURED HORIZONTALLY |
| | BETWEEN THE VERTICAL PLANES OF THE FOREMOST PROJECTION |
| | OF ADJACENT TREADS. REVISE DIMENSIONS SHOWN ON STAIR |
| | SECTION 'A' ON SHEET A-2. THEY ARE MEASURED FROM THE |
| | VERTICAL PLAN OF THE RISER TO THE END OF THE NOSING. |
| | |
| | RESPONSE: |
| | TREAD DIMENSION IS NOT MEASURED PROPERLY. NEED TO |
| | MEASURE FROM THE VERTICAL PLANES (RISER TO RISER). THE |
| | NOSING DIMENSION AND TREAD DIMENSION SHOWN ON BOTH |
| | STAIRS DETAILS DETAILS DON'T MATCH. REVISE AS REQUIRED |
| | TO MATCH. |
| | |
| | 4- SHEET A-2: |
| | A) OK. |
| | |
| | B)OK. |
| | |
| | C)OK. |
| | |
| | D) OK. |
| | |
| | 5- A)ACCORDING TO FIGURE R301.2(7) OF FBC-RESIDENTIAL |
| | THE MINIMUM DIMENSION "A" FOR WALL AND ROOF END ZONE IS |
| | 4 FT NOT 3.5 FT. REVISE THIS DIMENSION ON SHEET A-3 AND |
| | S-3. |
| | NOTE: WALL ELEVATION ON SHEET A-3 SPECIFIES A=3'-6". |
| | REVISE AS REQUIRED. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | B) OK. |
| | |
| | C) OK. |
| | |
| | 6- OK. |
| | |
| | 7- A) PROVIDE SPECIFICATIONS FOR THE INSULATION BETWEEN |
| | THE GARAGE AND THE A/C AREA OF THE MAIN HOUSE. SEC. |
| | R103.2 FBC-ENERGY CONSERVATION. COORDINATE WITH ENERGY |
| | CALCULATIONS. |
| | |
| | RESPONSE: |
| | PLANS DON'T SHOW ANY INSULATION BETWEEN THE GARAGE AND |
| | A/C AREA. |
| | |
| | B) PROVIDE THE MANUFACTURER'S SPECIFICATION S FOR |
| | WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON |
| | ITEM #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. |
| | R405.4.3 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | INFORMATION SUBMITTED DOESN'T MATCH PRODUCT APPROVALS |
| | SUBMITTED. THE INFORMATION SUBMITTED IS FOR ANOTHER |
| | WINDOW MODEL. IT DOESN'T MATCH THE MODEL SHOWN ON THE |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 8- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE CEILING AT THE PATIO AREA. SEC. |
| | R703.1.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | PLANS DON'T SHOW ANY DETAILS. |
| | |
| | 9- OK. |
| | |
| | 10- OK. |
| | |
| | 11- OK. |
| | |
| | 12- OK. |
| | |
| | 13- |
| | |
| | 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL) |
| | |
| | A) INSWING ENTRY DOOR AS SHOWN ON PLANS. FLORIDA |
| | PRODUCT APPROVAL FL22383-R1 SUBMITTED WAS DENIED. NEED |
| | TO PROVIDE CURRENT PRODUCT APPROVAL AND ALSO PROVIDE |
| | THE INSTALLATION DRAWINGS THAT CORRESPOND TO THIS |
| | PRODUCT APPROVAL. |
| | |
| | RESPONSE: |
| | INFORMATION FROM TWO DIFFERENT MANUFACTURER'S WAS |
| | SUBMITTED. CLEARLY MARK THE ENTRY DOOR AND THE GARAGE |
| | SIDE DOOR AND PROVIDE COMPLETE PRODUCT APPROVAL, |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| | CORRESPONDING DRAWINGS. |
| | |
| | B) GARAGE OUTSIDE SWING DOOR. PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE (TWO COPIES) THAT CORRESPONDS TO |
| | DRAWINGS SUBMITTED. |
| | |
| | RESPONSE: |
| | INFORMATION FROM TWO DIFFERENT MANUFACTURER'S WAS |
| | SUBMITTED. CLEARLY MARK THE ENTRY ODOR AND THE GARAGE |
| | SIDE DOOR AND PROVIDE COMPLETE PRODUCT APPROVAL, |
| | INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| | CORRESPONDING DRAWINGS. |
| | |
| | C)OK. |
| | |
| | D)OK. |
| | |
| | E) OK. |
| | |
| | 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | (A)ENGINEER'S LETTER LISTING ALL THE PRODUCT APPROVALS |
| | IS MISSING THE ENGINEER'S TITLE BLOCK WITH ALL HIS |
| | INFORMATION. CHAPTER 471 F.S. |
| | |
| | (B)PRODUCT APPROVALS LISTED DON'T MATCH PRODUCT |
| | APPROVALS SUBMITTED. REVISE AS REQUIRED TO MATCH. |
| | |
| | 16- OK. |
| | |
| | 17 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR |
| | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| | COMMENTS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |