| 2020-03-17 11:55:48 | INCOMPLETE APPLICATION |
| | |
| | PERMIT 19020197 - UNDERGROUND FIBER MCIMETRO PROJECT |
| | #1801CVFF.244 CLEMATIS TO OKEECHOBEE |
| | |
| | PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| | DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| | OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| | COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| | THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| | REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| | HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| | THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| | NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| | APPROVED. |
| | |
| | 1) UPDATED COMMENT: ENGINEERING PLANS - |
| | |
| | A. THE ENGINEERING PLANS MUST SHOW THE COMPLETED AND |
| | PROPOSED RIGHT-OF-WAY IMPROVEMENTS FOR THE CLEMATIS |
| | STREET RECONSTRUCTION PROJECTS, THE PROPOSED |
| | RECONSTRUCTION OF THE ALLEY SOUTH OF CLEMATIS STREET, |
| | AND THE UNDER CONSTRUCTION QUADRILLE/FERN MAST ARM |
| | INSTALLATION PROJECT. STAFF NEEDS TO VERIFY THAT THE |
| | PROPOSED FIBER CONDUIT, MARKER POLES, HANDHOLDS AND |
| | FUTURE COMMUNICATION POLES DO NOT INTERFERE WITH THESE |
| | APPROVED, PROPOSED AND CONSTRUCTED RIGHT-OF-WAY |
| | PROJECTS. |
| | |
| | 2) UPDATED COMMENT: SURVEY OF UNDERGROUND FACILITIES - |
| | THE SURVEY NEEDS TO BE AT A SIZE/SCALE THAT IS LEGIBLE. |
| | STAFF IS UNABLE TO MAKE OUT ANY DETAILS ON THE SURVEY |
| | THAT WAS PROVIDED. |
| | |
| | A. ALL UNDERGROUND UTILITIES NEED TO BE PROVIDED ON THE |
| | SURVEY. IF THE BORE IS PROPOSED WITHIN FIVE (5) FEET OF |
| | AN EXISTING UTILITY, YOU NEED TO PROVIDE A LETTER FROM |
| | THAT UTILITY THAT THE PROPOSED BORE DOES NOT INTERFERE |
| | WITH THE PROVISIONS OF THEIR SERVICES. |
| | |
| | B. THE SURVEY, PREPARED BY A FLORIDA LICENSED SURVEYOR, |
| | MUST SHOW THE RIGHT-OF-WAY LINE AND THE SIDEWALK, AND |
| | ANY UNDERGROUND FEATURES WITHIN THE RIGHT-OF-WAY ALONG |
| | THE FIBER CONDUIT PATH. |
| | |
| | C. THE LOCATIONS OF THE PALM TREES AND THEIR ROOT ZONE |
| | NEED TO BE SHOWN. THE FIBER BORE NEEDS TO BE CLEARLY |
| | SHOWN AVOIDING DAMAGE TO THE PALM ROOT ZONES (THIS MAY |
| | OCCUR ON THE ENGINEERING PLAN). |
| | |
| | D. THE ENGINEERING PLANS MUST SHOW THE SAME CONDITIONS |
| | AS THE SURVEY, SO THAT STAFF CAN VERIFY THAT NONE OF |
| | THE PROPOSED WORK (MARKER POLES, HANDHOLDS OR CONDUIT |
| | IS BEING INSTALLED ON PRIVATE PROPERTY AND THAT NO |
| | TREES (SPECIFICALLY THEIR ROOT SYSTEM) ARE BEING |
| | AFFECTED. |
| | |
| | E. PROVIDE THE SURVEY BACK UP FOR SHEETS 16 THROUGH 23, |
| | SO THAT STAFF CAN VERIFY THAT THE PROPOSED WORK IS IN |
| | THE RIGHT-OF-WAY. THE LOCATION MAP LINE APPEARS TO |
| | CROSS OUT OF THE RIGHT-OF-WAY LINE ONTO PRIVATE |
| | PROPERTY. |
| | |
| | 3) REPEAT COMMENT: ESTIMATED SCHEDULE - NO SCHEDULE WAS |
| | PROVIDED. PROVIDE A NARRATIVE OF THE ESTIMATED SCHEDULE |
| | OF THE PROPOSED WORK. |
| | |
| | 4) POLE STYLE - PLEASE NOTE THAT THE FUTURE POLES ARE |
| | REQUIRED TO MEET THE CITY CONCEALMENT STANDARDS |
| | OUTLINED IN SECTION 78-411 OF THE CITY CODE. |
| | |
| | NOTE: STAFF WILL NOT APPROVE THE INSTALLATION OF A SIX |
| | (6) FOOT TALL MARKER POLE ADJACENT TO THE HANDHOLES. IF |
| | THE HANDHOLES NEED TO BE MARKED, THEN PROVIDE THE |
| | INFORMATION ON THE HANDHOLE COVER. |
| | |
| | 5) ELECTRONIC FORMAT OF SUBMITTAL -. A COPY OF ALL OF |
| | THE SUBMITTAL MATERIAL MUST BE SUBMITTED IN ELECTRONIC |
| | FORMAT. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |
| | |