| Notes |
| Date |
Text |
| 2019-08-01 18:54:21 | APPROVED WITH EXCEPTIONS | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. THE | | | FOLLOWING ITEMS WILL NEED TO BE ADDRESSED. | | | 1) THE PLAT IS REQUIRED TO BE RE-RECORDED SHOWING THE | | | REQUIRED CHANGES DISCUSSED AT THE P.P.C. MEETING AND A | | | REVISED SURVEY SUBMITTED AND APPROVED BEFORE THE C.O. | | | CAN BE ISSUED. | | | 2) THE FOAM PLASTIC EXTERIOR TRIM THAT IS SHOWN IN THE | | | DETAILS ON SHEET A322 IS NOT ALLOWED. REVISED PLANS | | | COMPLYING WITH FBC 2603.5 ARE REQUIRED TO BE SUBMITTED | | | AND APPROVED. | | | 3) DEFERRED SUBMITTALS. FBC 107.3.4 - PROVIDE TWO SETS | | | OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE | | | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW | | | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR | | | TYPES.THE FOLLOWING ITEMS REQUIRE PRODUCT APPROVALS: | | | (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP | | | VENTILATORS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) PRE-ENGINEERED A/C STANDS | | | |
|