Plan Review Notes
Plan Review Notes For Permit 19020191
Permit Number 19020191
Review Stop B
Sequence Number 3
Notes
Date Text
2019-06-21 18:42:39* THIS IS THE SECOND REVIEW. I WAS ACCIDENTIALLY LOCKED
 OUT OF THE ORIGINAL SECOND REVIEW.
  
 FBC SIXTH EDITION (2017) - BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020191
 ADD: 351 PEMBROKE PLACE
 CONT: HEDRICK BROTHERS
 TEL:
 E-MAIL:
 CONST. TYPE: 1-B
 OCC. TYPE: R-2 W/ A3 & B ACCESSORY OCC.
 SPRINKLERED
  
 2ND REVIEW
 DATE:
 ACTION: DENIED
  
 1) N/A
  
 2) COMPLIED. THE VALUE HAS BEEN ADJUSTED TO AMOUNT
 SPECIFIED IN RESPONSE LETTER.
  
 3) THE ORIGINAL THRESHOLD INSPECTION FORMS WITH
 SIGNATURES WILL HAVE TO BE SUBMITTED.
 THE REQUIREMENTS FOR THRESHOLD BUILDINGS APPLY TO THIS
 BUILDING.
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS) 110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 4) COMPLIED.
  
 5) PARTIALLY COMPLIED. THERE ARE STILL REFERENCES TO
 THE 2015 IBC ON SHEET G100 AND G101. VERIFY THAT THE
 CORRECT CODE SECTION NUMBERS FOR THE 2017 FBC ARE
 SPECIFIED. ON PAGE 005, SHEET G100, THE 2015 FBC IS
 SPECIFIED AND THIS PROJECT IS UNDER THE 2017 FBC.
  
 6) PARTICALLY COMPLIED. THERE ARE STILL REFERENCES TO
 THE 2015 IBC ON SHEET G100 AND G101. VERIFY THAT THE
 CORRECT CODE SECTION NUMBERS FOR THE 2017 FBC ARE
 SPECIFIED. ON PAGE 005, SHEET G100, THE CODE SECTIONS
 ARE SPECIFIED AS IBC 2015 RATHER THAN FBC 2017.
  
 7) COMPLIED.
  
 8) PARTIALLY COMPLIED. THE PLAT IS REQUIRED TO BE
 RE-RECORDED SHOWING THE REQUIRED CHANGES DISCUSSED AT
 THE P.P.C. MEETING AND A REVISED SURVEY SUBMITTED
 BEFORE THE C.O. IS ISSUED. THERE IS A 6' FPL UTILITY
 EASEMENT SHOWN ON THE SURVEY AT THE NORTH EAST END OF
 THE PROPOSED BUILDING THAT IS WITHIN THE FOOTPRINT OF
 THE STRUCTURE. EXPLAIN HOW THIS ISSUE WILL BE RESOLVED.
 FBC 107.2.1
  
 9) PARTIALLY COMPLIED. SHEET 111B HAS A WALL TAG FOR
 D02. I DID NOT SEE WALL TYPE D02 LISTED IN THE WALL
 SCHEDULE ON SHEET A005. PLEASE CLARIFY. FBC 713.13.4
 REQUIRES THE TRASH CHUTE DISCHARGE ROOM TO BE SEPARATED
 BY FIRE BARRIERS WITH A FIRE-RESISTANCE RATING NOT LESS
 THAN THE REQUIRED FIRE RATING OF THE SHAFT ENCLOSURE
 WHICH IS TWO HOURS. OPENINGS INTO THE DISCHARGE ROOM
 FROM THE REMAINDER OF THE BUILDING SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 EQUAL TO THE PROTECTION REQUIRED FOR THE SHAFT
 ENCLOSURE. DOORS SHALL BE SELF- OR AUTOMATIC-CLOSING
 UPON THE DETECTION OF SMOKE IN ACCORDANCE WITH SECTION
 716.5.9.3.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) PARTIALLY COMPLIED. THE POSITIVE COMPONENT AND
 CLADDING PRESSURES ARE NOT PROVIDED FOR ROOF ZONES 1, 2
 AND 3. ON SHEET 30, S011 THE ROOF COMPONENT AND
 CLADDING PRESSURES IN THE CHART ARE THE SAME FOR ROOF
 ZONES 2 AND 3. THE ROOF DIAGRAM DOES NOT SPECIFY THAT
 THE CORNERS OF THE BUILDING ARE ZONE 3. THE BUILDING IS
 REQUIRED TO HAVE A CONTINOUS 3' HIGH PARAPET AROUND THE
 ROOF IN ORDER TO USE ZONE 2 PRESSURES FOR ZONE 3 PER
 ASCE 7-10. PLEASE CLARIFY. FBC 1507 & 1609.2
  
 14) NOT COMPLIED. THE 2017 FBC SECTION 310.4 CLASSIFIES
 DORMATORIES AS RESIDENTIAL R-2 OCCUPANCIES. THE
 RESIDENTS OCCUPY THE DWELLING UNITS FOR MORE THAN 30
 DAYS AND ARE CONSIDERED NON-TRANSIENT PER FBC CHAPTER
 2. ALL OF THE DORMATORY DWELLING UNITS ARE REQUIRED TO
 COMPLY WITH FAIR HOUSING AT A MINIMUM. ON SHEET G101
 THE ACCESSIBLE DWELLING UNITS TABLE LISTS 15 ACCESSIBLE
 UNITS AND HAS 0 TYPE A OR B UNITS. SHOW COMPLIANCE WITH
 THE 2017 FLORIDA ACCESSIBILITY CODE WHICH INCLUDES FAIR
 HOUSING. IN ADDITION TO THE ADA COMPLIANT RESIDENTIAL
 UNITS, PROVIDE PLANS WHICH SHOW THAT THE REMAINING
 APARTMENTS COMPLY WITH FAIR HOUSING ACCESSIBILITY
 GUIDELINES. FBC ACCESSIBILITY SECTION 224.7 & FAIR
 HOUSING GUIDELINES, SEE PLUMBING COMMENTS.
  
 15) COMPLIED.
  
 16) NOT COMPLIED. THE ENERGY CALCULATIONS THAT WERE
 SUBMITTED ARE NOT SIGNED AND SEALED BY THE ENGINEER OR
 ARCHITECT. SIGNED AND SEALED ENERGY CALCULATIONS ARE
 REQUIRED TO BE SUBMITTED. FS 471 AND FAC 61G 15-23
  
 17) WILL COMPLY. DEFERRED.
  
 18) WILL COMPLY. DEFERRED.
  
 19) WILL COMPLY. DEFERRED.
  
 20) WILL COMPLY. DEFERRED.
  
 21) NOT COMPLIED. THE MANUFACTURER'S BROCHURE THAT WAS
 SUBMITTED IS NOT ADEQUATE TO SHOW CODE COMPLIANCE. THE
 ACTUAL LABORTORY TEST REPORTS FOR THE FLOORING SOUND
 INSULATION ARE REQUIRED TO BE SUBMITTED. THIS CAN BE A
 DEFERRED SUBMITAL IF YOU WOULD LIKE. BLDG TYPE: TYPE I/
 TYPE II FLOOR INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING.
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 22) WILL COMPLY. DEFERRED.
  
 23) WILL COMPLY. DEFERRED.
  
 24) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  