| 2019-06-21 18:42:39 | * THIS IS THE SECOND REVIEW. I WAS ACCIDENTIALLY LOCKED |
| | OUT OF THE ORIGINAL SECOND REVIEW. |
| | |
| | FBC SIXTH EDITION (2017) - BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020191 |
| | ADD: 351 PEMBROKE PLACE |
| | CONT: HEDRICK BROTHERS |
| | TEL: |
| | E-MAIL: |
| | CONST. TYPE: 1-B |
| | OCC. TYPE: R-2 W/ A3 & B ACCESSORY OCC. |
| | SPRINKLERED |
| | |
| | 2ND REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) N/A |
| | |
| | 2) COMPLIED. THE VALUE HAS BEEN ADJUSTED TO AMOUNT |
| | SPECIFIED IN RESPONSE LETTER. |
| | |
| | 3) THE ORIGINAL THRESHOLD INSPECTION FORMS WITH |
| | SIGNATURES WILL HAVE TO BE SUBMITTED. |
| | THE REQUIREMENTS FOR THRESHOLD BUILDINGS APPLY TO THIS |
| | BUILDING. |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | A) FBC (CITY AMENDMENTS) 110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) PARTIALLY COMPLIED. THERE ARE STILL REFERENCES TO |
| | THE 2015 IBC ON SHEET G100 AND G101. VERIFY THAT THE |
| | CORRECT CODE SECTION NUMBERS FOR THE 2017 FBC ARE |
| | SPECIFIED. ON PAGE 005, SHEET G100, THE 2015 FBC IS |
| | SPECIFIED AND THIS PROJECT IS UNDER THE 2017 FBC. |
| | |
| | 6) PARTICALLY COMPLIED. THERE ARE STILL REFERENCES TO |
| | THE 2015 IBC ON SHEET G100 AND G101. VERIFY THAT THE |
| | CORRECT CODE SECTION NUMBERS FOR THE 2017 FBC ARE |
| | SPECIFIED. ON PAGE 005, SHEET G100, THE CODE SECTIONS |
| | ARE SPECIFIED AS IBC 2015 RATHER THAN FBC 2017. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) PARTIALLY COMPLIED. THE PLAT IS REQUIRED TO BE |
| | RE-RECORDED SHOWING THE REQUIRED CHANGES DISCUSSED AT |
| | THE P.P.C. MEETING AND A REVISED SURVEY SUBMITTED |
| | BEFORE THE C.O. IS ISSUED. THERE IS A 6' FPL UTILITY |
| | EASEMENT SHOWN ON THE SURVEY AT THE NORTH EAST END OF |
| | THE PROPOSED BUILDING THAT IS WITHIN THE FOOTPRINT OF |
| | THE STRUCTURE. EXPLAIN HOW THIS ISSUE WILL BE RESOLVED. |
| | FBC 107.2.1 |
| | |
| | 9) PARTIALLY COMPLIED. SHEET 111B HAS A WALL TAG FOR |
| | D02. I DID NOT SEE WALL TYPE D02 LISTED IN THE WALL |
| | SCHEDULE ON SHEET A005. PLEASE CLARIFY. FBC 713.13.4 |
| | REQUIRES THE TRASH CHUTE DISCHARGE ROOM TO BE SEPARATED |
| | BY FIRE BARRIERS WITH A FIRE-RESISTANCE RATING NOT LESS |
| | THAN THE REQUIRED FIRE RATING OF THE SHAFT ENCLOSURE |
| | WHICH IS TWO HOURS. OPENINGS INTO THE DISCHARGE ROOM |
| | FROM THE REMAINDER OF THE BUILDING SHALL BE PROTECTED |
| | BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING |
| | EQUAL TO THE PROTECTION REQUIRED FOR THE SHAFT |
| | ENCLOSURE. DOORS SHALL BE SELF- OR AUTOMATIC-CLOSING |
| | UPON THE DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| | 716.5.9.3. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) PARTIALLY COMPLIED. THE POSITIVE COMPONENT AND |
| | CLADDING PRESSURES ARE NOT PROVIDED FOR ROOF ZONES 1, 2 |
| | AND 3. ON SHEET 30, S011 THE ROOF COMPONENT AND |
| | CLADDING PRESSURES IN THE CHART ARE THE SAME FOR ROOF |
| | ZONES 2 AND 3. THE ROOF DIAGRAM DOES NOT SPECIFY THAT |
| | THE CORNERS OF THE BUILDING ARE ZONE 3. THE BUILDING IS |
| | REQUIRED TO HAVE A CONTINOUS 3' HIGH PARAPET AROUND THE |
| | ROOF IN ORDER TO USE ZONE 2 PRESSURES FOR ZONE 3 PER |
| | ASCE 7-10. PLEASE CLARIFY. FBC 1507 & 1609.2 |
| | |
| | 14) NOT COMPLIED. THE 2017 FBC SECTION 310.4 CLASSIFIES |
| | DORMATORIES AS RESIDENTIAL R-2 OCCUPANCIES. THE |
| | RESIDENTS OCCUPY THE DWELLING UNITS FOR MORE THAN 30 |
| | DAYS AND ARE CONSIDERED NON-TRANSIENT PER FBC CHAPTER |
| | 2. ALL OF THE DORMATORY DWELLING UNITS ARE REQUIRED TO |
| | COMPLY WITH FAIR HOUSING AT A MINIMUM. ON SHEET G101 |
| | THE ACCESSIBLE DWELLING UNITS TABLE LISTS 15 ACCESSIBLE |
| | UNITS AND HAS 0 TYPE A OR B UNITS. SHOW COMPLIANCE WITH |
| | THE 2017 FLORIDA ACCESSIBILITY CODE WHICH INCLUDES FAIR |
| | HOUSING. IN ADDITION TO THE ADA COMPLIANT RESIDENTIAL |
| | UNITS, PROVIDE PLANS WHICH SHOW THAT THE REMAINING |
| | APARTMENTS COMPLY WITH FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES. FBC ACCESSIBILITY SECTION 224.7 & FAIR |
| | HOUSING GUIDELINES, SEE PLUMBING COMMENTS. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) NOT COMPLIED. THE ENERGY CALCULATIONS THAT WERE |
| | SUBMITTED ARE NOT SIGNED AND SEALED BY THE ENGINEER OR |
| | ARCHITECT. SIGNED AND SEALED ENERGY CALCULATIONS ARE |
| | REQUIRED TO BE SUBMITTED. FS 471 AND FAC 61G 15-23 |
| | |
| | 17) WILL COMPLY. DEFERRED. |
| | |
| | 18) WILL COMPLY. DEFERRED. |
| | |
| | 19) WILL COMPLY. DEFERRED. |
| | |
| | 20) WILL COMPLY. DEFERRED. |
| | |
| | 21) NOT COMPLIED. THE MANUFACTURER'S BROCHURE THAT WAS |
| | SUBMITTED IS NOT ADEQUATE TO SHOW CODE COMPLIANCE. THE |
| | ACTUAL LABORTORY TEST REPORTS FOR THE FLOORING SOUND |
| | INSULATION ARE REQUIRED TO BE SUBMITTED. THIS CAN BE A |
| | DEFERRED SUBMITAL IF YOU WOULD LIKE. BLDG TYPE: TYPE I/ |
| | TYPE II FLOOR INSULATION (FBC-B 2014) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING. |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 22) WILL COMPLY. DEFERRED. |
| | |
| | 23) WILL COMPLY. DEFERRED. |
| | |
| | 24) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |