Plan Review Notes
Plan Review Notes For Permit 19020191
Permit Number 19020191
Review Stop P
Sequence Number 2
Notes
Date Text
2019-05-21 14:56:16PLUMBING 2ND REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 1)**OK
  
 2)**SEPARATE FACILITIES ARE REQUIRED FOR THE A3
 OCCUPANCY PER FBC-PLB 403.2. THERE IS NO EXCEPTION
 LISTED TO NOT PROVIDE A SEPARATE WOMENS ACCESSIBLE
 TOILET ROOM.
  
 3)**OK
  
 4)**OK
  
 5)**OK
  
 6) PROVIDE INSTALLATION MANUAL FOR THE LINT
 INTERCEPTOR. TYPICAL DETAIL PROVIDE ON SHT. A404 DOES
 NOT PROVIDE ANY INFORMATION SHOWING SIZE, GPM OR IF IT
 WILL COMPLY WITH FBC-PLB 1003.6, 1003.2.
  
 7) PROVIDE CABINET DETAIL SHOWING ALL BATHROOM SINKS TO
 BE MAX 34". THE NON-ACCESSIBLE UNIT WILL STILL BE UNDER
 THE FAIR HOUSING ACT (FHA) WHICH ALSO REQUIRES 34" MAX.
 PLEASE REVIEW FHA DESIGN MANUAL 7.52. THE ACCESSIBLE
 SINKS SHALL MEET ALL EXCEPTION UNDER #3 FBC-ACC606.2
  
 8) THE FOLLOWING SHEETS AND DETAILS ARE STILL MISSING
 CLEAR FLOOR AND OR TURNING SPACE.
  
 A*SHT. A412 THE CLEAR FLOOR SPACE FOR THE BATHTUB SHALL
 EXTEND THE LENGTH OF THE TUB FBC-ACC 607.2
  
 B*SHT A421, A401 TOILETS ARE NOT PERMITTED TO BE
 ADJACENT TO AN ACCESSIBLE TUB FBC-ACC 607.2 AND A
 VANITY CABINET NOR TOILET MAY ENCROACH ONTO THE SHOWERS
 CLEAR FLOOR SPACE. FHA 7.44, 7.58, 7.59
  
 C* SHT.A421 THE WASHER AND DRYER IN THE STAFF
 ACCESSIBLE UNIT IS SHOWING A SIGNAL FORWARD APPROACH.
 ONLY A PARALLEL APPROACH IS PERMITTED AND MUST BE
 CENTERED ON EACH OF THE APPLIANCE'S. FBC-ACC 611.2
  
 D*SHT. A419 PROVIDE FHA CLEAR FLOOR SPACE FOR THE TUB
 AND SHOWER. FHA
  
 9)**OK
  
 10)**OK
  
 11)**OK
  
 12)**OK
  
 13) DEFERRED SUBMITTAL FOR THE BOOSTER PUMPS APPROVED.
  
 14)**OK
  
 15) PROVIDE WHAT SAFE HARBOR YOU ARE USING AS A
 STANDARD. PROVIDE INFORMATION ON SHT.G100 UNDER
 APPLICABLE CODES. 2ND REQUEST. FBC 107.3.5
  
 16)**OK
  
 17) NEW COMMENT. SHT A401 DETAIL #7,9 AND SHT. A003 ALL
 SHOW THE MEASUREMENT OF THE GRAB BAR AS BEING CENTERED.
 THE 33"-36" IS TO BE AT THE TOP OF THE GRIPPING
 SURFACE. FBC-ACC 609.4
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  