| 2019-05-21 14:56:16 | PLUMBING 2ND REVIEW**DENIED** |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | 1)**OK |
| | |
| | 2)**SEPARATE FACILITIES ARE REQUIRED FOR THE A3 |
| | OCCUPANCY PER FBC-PLB 403.2. THERE IS NO EXCEPTION |
| | LISTED TO NOT PROVIDE A SEPARATE WOMENS ACCESSIBLE |
| | TOILET ROOM. |
| | |
| | 3)**OK |
| | |
| | 4)**OK |
| | |
| | 5)**OK |
| | |
| | 6) PROVIDE INSTALLATION MANUAL FOR THE LINT |
| | INTERCEPTOR. TYPICAL DETAIL PROVIDE ON SHT. A404 DOES |
| | NOT PROVIDE ANY INFORMATION SHOWING SIZE, GPM OR IF IT |
| | WILL COMPLY WITH FBC-PLB 1003.6, 1003.2. |
| | |
| | 7) PROVIDE CABINET DETAIL SHOWING ALL BATHROOM SINKS TO |
| | BE MAX 34". THE NON-ACCESSIBLE UNIT WILL STILL BE UNDER |
| | THE FAIR HOUSING ACT (FHA) WHICH ALSO REQUIRES 34" MAX. |
| | PLEASE REVIEW FHA DESIGN MANUAL 7.52. THE ACCESSIBLE |
| | SINKS SHALL MEET ALL EXCEPTION UNDER #3 FBC-ACC606.2 |
| | |
| | 8) THE FOLLOWING SHEETS AND DETAILS ARE STILL MISSING |
| | CLEAR FLOOR AND OR TURNING SPACE. |
| | |
| | A*SHT. A412 THE CLEAR FLOOR SPACE FOR THE BATHTUB SHALL |
| | EXTEND THE LENGTH OF THE TUB FBC-ACC 607.2 |
| | |
| | B*SHT A421, A401 TOILETS ARE NOT PERMITTED TO BE |
| | ADJACENT TO AN ACCESSIBLE TUB FBC-ACC 607.2 AND A |
| | VANITY CABINET NOR TOILET MAY ENCROACH ONTO THE SHOWERS |
| | CLEAR FLOOR SPACE. FHA 7.44, 7.58, 7.59 |
| | |
| | C* SHT.A421 THE WASHER AND DRYER IN THE STAFF |
| | ACCESSIBLE UNIT IS SHOWING A SIGNAL FORWARD APPROACH. |
| | ONLY A PARALLEL APPROACH IS PERMITTED AND MUST BE |
| | CENTERED ON EACH OF THE APPLIANCE'S. FBC-ACC 611.2 |
| | |
| | D*SHT. A419 PROVIDE FHA CLEAR FLOOR SPACE FOR THE TUB |
| | AND SHOWER. FHA |
| | |
| | 9)**OK |
| | |
| | 10)**OK |
| | |
| | 11)**OK |
| | |
| | 12)**OK |
| | |
| | 13) DEFERRED SUBMITTAL FOR THE BOOSTER PUMPS APPROVED. |
| | |
| | 14)**OK |
| | |
| | 15) PROVIDE WHAT SAFE HARBOR YOU ARE USING AS A |
| | STANDARD. PROVIDE INFORMATION ON SHT.G100 UNDER |
| | APPLICABLE CODES. 2ND REQUEST. FBC 107.3.5 |
| | |
| | 16)**OK |
| | |
| | 17) NEW COMMENT. SHT A401 DETAIL #7,9 AND SHT. A003 ALL |
| | SHOW THE MEASUREMENT OF THE GRAB BAR AS BEING CENTERED. |
| | THE 33"-36" IS TO BE AT THE TOP OF THE GRIPPING |
| | SURFACE. FBC-ACC 609.4 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |