Plan Review Notes
Plan Review Notes For Permit 19020191
Permit Number 19020191
Review Stop M
Sequence Number 2
Notes
Date Text
2019-06-04 16:00:072ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19020191
 6/4/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G101: PLEASE CORRECT THE ENERGY SUMMARY WHICH
 IS INDICATING A "PRESCRIPTIVE COMPLIANCE" METHOD. AN
 ENERGYGAUGE "PERFOMANCE" BASED COMPLIANCE REPORT WAS
 SUBMITTED.
  
 2) ACKNOWLEDGED THAT A COMMISSIONING PLAN WILL BE
 SUBMITTED AFTER PERMIT ISSUANCE, AND A FINAL
 COMMISSIONING REPORT WILL BE PROVIDED TO THE OWNERSHIP
 OF THE BUILDING AND TO THE WPB BUILDING DEPARTMENT AS A
 CONTINGENCY OF ISSUING THE CO.
  
 3) ACKNOWLEDGED THAT DEFERRED SUBMITTALS WILL BE
 ACCEPTED.
  
 REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP
 DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME
 OF INSPECTION.
 A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 B) MOTORIZED AND BAROMETRIC DAMPERS
 C) DUCT SMOKE DETECTORS
 D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 E) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 F) CLOTHES DRYERS
 G) COOKING APPLIANCES
 H) TEST AND BALANCE REPORTS
  
 SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR
 DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE
 TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED
 ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE
 STRUCTURAL ENGINEER RECORD.
 B) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR
 DUCTS AND VENT FLUES.
 C) COMMISSIONING REPORTS
  
 4) COMMENT #5A & 5B FROM THE 1ST REVIEW STILL EXISTS,
 PLEASE COMPLY:
 SHEET M001: THE VENTILATION CALCULATIONS ARE NOT IN
 COMPLIANCE WITH TABLE 403.3.1.1 FBC M.
 PLEASE MAKE THESE CORRECTIONS:
 A) LOBBY- 30 PERSONS PER 1000 SF. (7.5 CFMS PER PERSON)
 + (.06 CFMS PER SF) = 760 CFMS
 B) MULTIPURPOSE- 120 PERSONS PER 1000 SF. (5 CFMS PER
 PERSON) + (.06 CFMS PER SF) = 330 CFMS.
  
 5) IN RESPONSE TO 1ST REVIEW COMMENT #8 PLEASE INDICATE
 THE O/A DUCTS PENETRATING THE 1 HR FIRE-RATED CORRIDOR
 WALLS WILL BE SHEET METAL TO MEET THE EXCEPTION TO NOT
 PROVIDE DAMPERS- SECTION 607.5.3 FBC M. PLACE A KEYED
 NOTE ON THE PLAN AND REVISE THE DUCT APPLICATION
 SCHEDULE ON SHEET M002.
  
 6) IN RESPONSE TO 1ST REVIEW COMMENTS #11, 15, & 18,
 PLEASE PROVIDE NOTES INDICATING THE ACCESS PANELS WILL
 BE LARGE ENOUGH FOR MAINTENANCE AND REPLACEMENT OF THE
 AIR HANDLERS- SECTION 306.1 FBC M.
  
 7) IN RESPONSE TO 1ST REVIEW COMMENT #13 PLEASE PROVIDE
 EXHAUST CALCULATIONS AND A SEQUENCE OF OPERATION FOR
 EF-4.
  
 8) IN RESPONSE TO 1ST REVIEW COMMENTS #23 & 26, HP-B IS
 NOT SHOWN IN THE EQUIPMENT SCHEDULES ON SHEET M603, AND
 IT IS NOT LISTED IN THE ENERGYGAUGE REPORT. AS STATED
 BEFORE THIS APPEARS TO BE A TYPO- SHOULD BE AHU-B
  
 9) IN RESPONSE TO 1ST REVIEW COMMENT #30, PLEASE PLACE
 A NOTE ON M501 INDICATING THE MOTORIZED DAMPER WILL BE
 INSTALLED AT THE ELEVATOR SHAFT VENT.
  
 10) IN RESPONSE TO 1ST REVIEW COMMENT #31, PLEASE
 PROVIDE A NARRATIVE THAT DESCRIBES THE SEQUENCE OF
 OPERATION OF THE DUCT SMOKE DETECTORS AND INTERACTION
 WITH THE FIRE ALARM SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved