| 2019-06-04 16:00:07 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020191 |
| | 6/4/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET G101: PLEASE CORRECT THE ENERGY SUMMARY WHICH |
| | IS INDICATING A "PRESCRIPTIVE COMPLIANCE" METHOD. AN |
| | ENERGYGAUGE "PERFOMANCE" BASED COMPLIANCE REPORT WAS |
| | SUBMITTED. |
| | |
| | 2) ACKNOWLEDGED THAT A COMMISSIONING PLAN WILL BE |
| | SUBMITTED AFTER PERMIT ISSUANCE, AND A FINAL |
| | COMMISSIONING REPORT WILL BE PROVIDED TO THE OWNERSHIP |
| | OF THE BUILDING AND TO THE WPB BUILDING DEPARTMENT AS A |
| | CONTINGENCY OF ISSUING THE CO. |
| | |
| | 3) ACKNOWLEDGED THAT DEFERRED SUBMITTALS WILL BE |
| | ACCEPTED. |
| | |
| | REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP |
| | DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME |
| | OF INSPECTION. |
| | A) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. |
| | B) MOTORIZED AND BAROMETRIC DAMPERS |
| | C) DUCT SMOKE DETECTORS |
| | D) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES |
| | INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT |
| | APPROVALS AND/OR MIAMI-DADE NOA'S |
| | E) AC STAND NOA'S OR FL. PRODUCT APPROVALS |
| | F) CLOTHES DRYERS |
| | G) COOKING APPLIANCES |
| | H) TEST AND BALANCE REPORTS |
| | |
| | SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT |
| | FOR REVIEW. |
| | A) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR |
| | INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND |
| | APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR |
| | DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE |
| | TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED |
| | ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE |
| | STRUCTURAL ENGINEER RECORD. |
| | B) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR |
| | DUCTS AND VENT FLUES. |
| | C) COMMISSIONING REPORTS |
| | |
| | 4) COMMENT #5A & 5B FROM THE 1ST REVIEW STILL EXISTS, |
| | PLEASE COMPLY: |
| | SHEET M001: THE VENTILATION CALCULATIONS ARE NOT IN |
| | COMPLIANCE WITH TABLE 403.3.1.1 FBC M. |
| | PLEASE MAKE THESE CORRECTIONS: |
| | A) LOBBY- 30 PERSONS PER 1000 SF. (7.5 CFMS PER PERSON) |
| | + (.06 CFMS PER SF) = 760 CFMS |
| | B) MULTIPURPOSE- 120 PERSONS PER 1000 SF. (5 CFMS PER |
| | PERSON) + (.06 CFMS PER SF) = 330 CFMS. |
| | |
| | 5) IN RESPONSE TO 1ST REVIEW COMMENT #8 PLEASE INDICATE |
| | THE O/A DUCTS PENETRATING THE 1 HR FIRE-RATED CORRIDOR |
| | WALLS WILL BE SHEET METAL TO MEET THE EXCEPTION TO NOT |
| | PROVIDE DAMPERS- SECTION 607.5.3 FBC M. PLACE A KEYED |
| | NOTE ON THE PLAN AND REVISE THE DUCT APPLICATION |
| | SCHEDULE ON SHEET M002. |
| | |
| | 6) IN RESPONSE TO 1ST REVIEW COMMENTS #11, 15, & 18, |
| | PLEASE PROVIDE NOTES INDICATING THE ACCESS PANELS WILL |
| | BE LARGE ENOUGH FOR MAINTENANCE AND REPLACEMENT OF THE |
| | AIR HANDLERS- SECTION 306.1 FBC M. |
| | |
| | 7) IN RESPONSE TO 1ST REVIEW COMMENT #13 PLEASE PROVIDE |
| | EXHAUST CALCULATIONS AND A SEQUENCE OF OPERATION FOR |
| | EF-4. |
| | |
| | 8) IN RESPONSE TO 1ST REVIEW COMMENTS #23 & 26, HP-B IS |
| | NOT SHOWN IN THE EQUIPMENT SCHEDULES ON SHEET M603, AND |
| | IT IS NOT LISTED IN THE ENERGYGAUGE REPORT. AS STATED |
| | BEFORE THIS APPEARS TO BE A TYPO- SHOULD BE AHU-B |
| | |
| | 9) IN RESPONSE TO 1ST REVIEW COMMENT #30, PLEASE PLACE |
| | A NOTE ON M501 INDICATING THE MOTORIZED DAMPER WILL BE |
| | INSTALLED AT THE ELEVATOR SHAFT VENT. |
| | |
| | 10) IN RESPONSE TO 1ST REVIEW COMMENT #31, PLEASE |
| | PROVIDE A NARRATIVE THAT DESCRIBES THE SEQUENCE OF |
| | OPERATION OF THE DUCT SMOKE DETECTORS AND INTERACTION |
| | WITH THE FIRE ALARM SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |