Review Stop G
Sequence Number 2
Notes
Date Text
2019-05-21 15:05:11GAS 2ND REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 1)**OK
  
 2)**OK
  
 3) DEFERRED SUBMITTAL IS NOT PERMITTED ON THE GAS WATER
 HEATER'S. IN ORDER TO PERFORM AN ACCURATE REVIEW WE
 NEED TO KNOW THE CORRECT BTU'S TO ENSURE YOUR SUPPLY
 PIPING IS ADEQUATELY SIZED. AS YOU POINTED OUT ON
 COMMENT RESPONSE # 4 THESE UNIT ARE DIRECT VENT SO WE
 NEED TO KNOW THE REQUIREMENT'S OF THE VENTING SYSTEM
 AND PIPING MATERIAL ALLOWED. PROVIDE INSTALLATION
 MANUALS. FBC 107.2.1. SEE NEW COMMENT #6
  
 4)**OK
  
 5)**OK
  
 6) NEW COMMENT. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER 2017
 FBC-FUEL GAS SECS. 502 THRU 505
  