2019-03-21 14:49:39PLUMBING 1ST REVIEW PERMIT#19020191**DENIED**PLEASE
 FEEL FREE TO CALL OR EMAIL TO DISCUSS ANY OF THESE
 COMMENTS.
  
 1) PROVIDE OCCUPANCY LOAD FOR EACH CLASSIFICATION UNDER
 THIS BUILDING ENVELOPE SHOWING MINIMUM PLUMBING
 FACILITIES REQUIRED TO COMPLY WITH FBC-(P)PLUMBING
 403.1
  
 2) PROVIDE A FEMALE RESTROOM FOR THE ASSEMBLY
 OCCUPANCY. 1 UNISEX RESTROOM IS ONLY PERMITED WHEN THE
 OCCUPANT LOAD IS 15 OR FEWER. BOTH THE BUSINESS AND
 ASSEMBLY OCCUPANCY COULD HAVE FEMALE STAFFING.
  
 3) C5.1 BACKFLOW DETAIL PLEASE ADD NOTE A SEPERATE
 PLUMBING PERMIT IS REQUIRED AND MUST BE INSTALLED BY A
 LICENSED PLUMBER. W.P.B ORD. CROSS CONNECTION MANUAL.
  
 4) SHT. LP-1 LIST 152 UNITS. SHEET G101 LIST 152 PLEASE
 CLEARIFY. FBC 107.2.1
  
 5) SHT. A003 LINE D PLEASE ADD OVERALL LENGHT OF GRAB
 BAR SHOWING 54". FBC-A 604.5.1.
  
 6) PROVIDE INSTALLATION MANUAL AND SPEC ON LINT
 INTERCEPTOR. PROVIDE DETAIL SHOWING HOW THIS IS GOING
 TO BE SERVICED. FBC 107.2.1
  
 7) SHT. 401 SINK DETAIL PLEASE ADD MEASUREMENT SHOWING
 SINK TO BE MAX 34". FBC-P 606.3
  
 8)SHT. 412 PROVIDE ALL CLEAR FLOOR SPACES IN ADA
 TYPICAL UNIT DETAIL. FBC-A 604.9.2, 606.2, 305, 306,
 608.2.3.
  
 9) SHT. A431 COMMON AREA RESTROOM SHOWS THE LAVATORIES
 CLEAR FLOOR SPACE BUT IS MISSING THE TOILET AND
 DRINKING FOUNTAINS. PLEASE SHOW THE TOILET AND DRINKING
 FOUNTAINS CLEAR FLOOR SPACE. FBC-A 305, 604.3.1,
 604.8.1.6.
  
 10) SHT. A431 ROOM 112 HAS THE DOOR SWINGING INTO THE
 CLEAR FLOOR SPACE. THE DOOR IS NOT PERMITTED TO SWING
 INTO ANY CLEAR FLOOR SPACE UNLESS A 30" X 48" CLEAR
 FLOOR SPACE IS PROVIDES OUTSIDE THE SWING OF THE DOOR.
 SEE EXPECTION #2. FBC-A 603.2.3
  
 11) SHT. P110B ROOM 101 APPEARS TO HAVE THE TOILET DRY
 VENT AND NOT COMPLYING WITH FBC-P 912.2 AND IS MISSING
 THE PIPING TO THE SHOWER. FBC 107.3.5
  
 12) SHT. P404 UNDER SPACING OF HANGERS LIST PVC
 HORIZONTAL PIPING 1 1/2" TO 3" AS BEING SPACED 5' AND
 3"-6" AS BEING 6'APART. FBC-P 308.5 REQUIRES ALL PVC
 HORIZONTAL PIPING HANGERS PLACED NO MORE THEN 4'.
  
 13) PROVIDE MANUFACTURES INSTALLATION MANUAL FOR THE
 DOMESTIC BOOSTER PUMPS. FBC 107.2.1
  
 14) UNABLE TO LOCATE SERVICE SINK. ALL ASSEMBLY
 OCCUPANIES REQUIRE A SERVICE SINK PER FBC-P TABLE403.1.
  
 15) THIS BUILDING WOULD FALL UNDER THE FAIR HOUSING
 AMENDMENT ACT. PLEASE PROVIDES WHAT SAFE HARBOR YOU ARE
 USING AS A STANDARD AND PROVIDE ALL REQUIRED CLEAR
 FLOOR SPACE'S FOR USAGABLE KITCHEN'S AND BATHROOMS FOR
 ALL UNIT'S. THIS WOULD ALSO INCLUDE THE LAUNDRY ROOM
 ACCESS TO THE WASHING MACHINE AND DRYER.
  
 16) BEING THAT YOU HAVE 2 STAFF ONLY DWELLINGS SHOULD 1
 NEED TO BE FLORIDA ASSCESSIBILITY?
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  