| 2019-03-21 14:49:39 | PLUMBING 1ST REVIEW PERMIT#19020191**DENIED**PLEASE |
| | FEEL FREE TO CALL OR EMAIL TO DISCUSS ANY OF THESE |
| | COMMENTS. |
| | |
| | 1) PROVIDE OCCUPANCY LOAD FOR EACH CLASSIFICATION UNDER |
| | THIS BUILDING ENVELOPE SHOWING MINIMUM PLUMBING |
| | FACILITIES REQUIRED TO COMPLY WITH FBC-(P)PLUMBING |
| | 403.1 |
| | |
| | 2) PROVIDE A FEMALE RESTROOM FOR THE ASSEMBLY |
| | OCCUPANCY. 1 UNISEX RESTROOM IS ONLY PERMITED WHEN THE |
| | OCCUPANT LOAD IS 15 OR FEWER. BOTH THE BUSINESS AND |
| | ASSEMBLY OCCUPANCY COULD HAVE FEMALE STAFFING. |
| | |
| | 3) C5.1 BACKFLOW DETAIL PLEASE ADD NOTE A SEPERATE |
| | PLUMBING PERMIT IS REQUIRED AND MUST BE INSTALLED BY A |
| | LICENSED PLUMBER. W.P.B ORD. CROSS CONNECTION MANUAL. |
| | |
| | 4) SHT. LP-1 LIST 152 UNITS. SHEET G101 LIST 152 PLEASE |
| | CLEARIFY. FBC 107.2.1 |
| | |
| | 5) SHT. A003 LINE D PLEASE ADD OVERALL LENGHT OF GRAB |
| | BAR SHOWING 54". FBC-A 604.5.1. |
| | |
| | 6) PROVIDE INSTALLATION MANUAL AND SPEC ON LINT |
| | INTERCEPTOR. PROVIDE DETAIL SHOWING HOW THIS IS GOING |
| | TO BE SERVICED. FBC 107.2.1 |
| | |
| | 7) SHT. 401 SINK DETAIL PLEASE ADD MEASUREMENT SHOWING |
| | SINK TO BE MAX 34". FBC-P 606.3 |
| | |
| | 8)SHT. 412 PROVIDE ALL CLEAR FLOOR SPACES IN ADA |
| | TYPICAL UNIT DETAIL. FBC-A 604.9.2, 606.2, 305, 306, |
| | 608.2.3. |
| | |
| | 9) SHT. A431 COMMON AREA RESTROOM SHOWS THE LAVATORIES |
| | CLEAR FLOOR SPACE BUT IS MISSING THE TOILET AND |
| | DRINKING FOUNTAINS. PLEASE SHOW THE TOILET AND DRINKING |
| | FOUNTAINS CLEAR FLOOR SPACE. FBC-A 305, 604.3.1, |
| | 604.8.1.6. |
| | |
| | 10) SHT. A431 ROOM 112 HAS THE DOOR SWINGING INTO THE |
| | CLEAR FLOOR SPACE. THE DOOR IS NOT PERMITTED TO SWING |
| | INTO ANY CLEAR FLOOR SPACE UNLESS A 30" X 48" CLEAR |
| | FLOOR SPACE IS PROVIDES OUTSIDE THE SWING OF THE DOOR. |
| | SEE EXPECTION #2. FBC-A 603.2.3 |
| | |
| | 11) SHT. P110B ROOM 101 APPEARS TO HAVE THE TOILET DRY |
| | VENT AND NOT COMPLYING WITH FBC-P 912.2 AND IS MISSING |
| | THE PIPING TO THE SHOWER. FBC 107.3.5 |
| | |
| | 12) SHT. P404 UNDER SPACING OF HANGERS LIST PVC |
| | HORIZONTAL PIPING 1 1/2" TO 3" AS BEING SPACED 5' AND |
| | 3"-6" AS BEING 6'APART. FBC-P 308.5 REQUIRES ALL PVC |
| | HORIZONTAL PIPING HANGERS PLACED NO MORE THEN 4'. |
| | |
| | 13) PROVIDE MANUFACTURES INSTALLATION MANUAL FOR THE |
| | DOMESTIC BOOSTER PUMPS. FBC 107.2.1 |
| | |
| | 14) UNABLE TO LOCATE SERVICE SINK. ALL ASSEMBLY |
| | OCCUPANIES REQUIRE A SERVICE SINK PER FBC-P TABLE403.1. |
| | |
| | 15) THIS BUILDING WOULD FALL UNDER THE FAIR HOUSING |
| | AMENDMENT ACT. PLEASE PROVIDES WHAT SAFE HARBOR YOU ARE |
| | USING AS A STANDARD AND PROVIDE ALL REQUIRED CLEAR |
| | FLOOR SPACE'S FOR USAGABLE KITCHEN'S AND BATHROOMS FOR |
| | ALL UNIT'S. THIS WOULD ALSO INCLUDE THE LAUNDRY ROOM |
| | ACCESS TO THE WASHING MACHINE AND DRYER. |
| | |
| | 16) BEING THAT YOU HAVE 2 STAFF ONLY DWELLINGS SHOULD 1 |
| | NEED TO BE FLORIDA ASSCESSIBILITY? |
| | |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |