| 2019-02-25 16:54:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE FOLLOWING COMMENTS MAY NOT REPRESENT THE ENTIRETY |
| | OF COMMENTS AS THE PLANS APPEAR TO BE INSUFFICIENT WITH |
| | FLORIDA FIRE PRENVENTION CODE REFERENCES. |
| | |
| | |
| | 1) SHEET G 100 - THERE DOES NOT APPEAR TO BE BE ANY |
| | REFERENCE FIRE CODE COMPLAINCE WITH ANY FLORIDA FIRE |
| | PREVENTION CODE AND/OR NATIONAL FIRE PREVENTION CODE. |
| | |
| | PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2015 EDITION OF NFPA 1, SPECIFICALLY, |
| | CHAPTER 20.8, HOTELS AND DORMITORIES AND NFPA 101, |
| | SPECIFICALLY, CHAPTER 28, NEW HOTELS AND DORMITORIES. |
| | THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| | NFPA 110, 2013 EDITION. |
| | AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B, |
| | 2015 EDITION |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE REVISION NOTE |
| | |
| | |
| | |
| | 2) SHEET G 101 - THERE IS AN INDICATION OF "NO" UNDER |
| | DISTRIBUTED ANTENNA SYSTEM . THERE IS NO DEFINITION TO |
| | THIS SYSTEM. |
| | |
| | HOWEVER, PER NFPA 72, |
| | |
| | 24.5.2* TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT |
| | SYSTEMS. |
| | 24.5.2.1 GENERAL. |
| | 24.5.2.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM |
| | CAPABLE |
| | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON |
| | FREQUENCIES |
| | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE |
| | INSTALLED |
| | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE |
| | AUTHORITY |
| | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL |
| | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT |
| | DEGRADE |
| | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. |
| | 24.5.2.1.2 APPROVAL AND PERMIT. PLANS SHALL BE |
| | SUBMITTED FOR |
| | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF |
| | SUCCESSFUL |
| | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED |
| | FOR THE |
| | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED |
| | BY |
| | THE AUTHORITY HAVING JURISDICTION. |
| | 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE |
| | PROVIDED |
| | THROUGHOUT THE BUILDING AS A PERCENTAGE OF FLOOR AREA |
| | AS SPECIFIED |
| | IN 24.5.2.2.1 THROUGH 24.5.2.2.3. |
| | 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE |
| | FIRE COMMAND |
| | CENTER(S), THE FIRE PUMP ROOM(S), EXIT STAIRS, EXIT |
| | PASSAGEWAYS, |
| | ELEVATOR LOBBIES, STANDPIPE CABINETS, SPRINKLER |
| | SECTIONAL |
| | VALVE LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE |
| | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH |
| | 99 PERCENT |
| | FLOOR AREA RADIO COVERAGE. |
| | 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING |
| | AREAS |
| | SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA RADIO |
| | COVERAGE. |
| | 24.5.2.2.3 AMPLIFICATION COMPONENTS. BUILDINGS AND |
| | STRUCTURES |
| | THAT CANNOT SUPPORT THE REQUIRED LEVEL OF RADIO |
| | COVERAGE |
| | SHALL BE EQUIPPED WITH A RADIATING CABLE SYSTEM OR A |
| | DISTRIBUTED |
| | ANTENNA SYSTEM (DAS) WITH FCC-CERTIFIED SIGNAL |
| | BOOSTERS, |
| | OR BOTH, OR WITH A SYSTEM THAT IS OTHERWISE APPROVED, |
| | IN ORDER |
| | TO ACHIEVE THE REQUIRED ADEQUATE RADIO COVERAGE. |
| | 24.5.2.3 SIGNAL STRENGTH. |
| | 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH |
| | OF |
| | ?95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE |
| | AUTHORITY |
| | HAVING JURISDICTION, SHALL BE PROVIDED THROUGHOUT THE |
| | COVERAGE |
| | AREA. |
| | 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH |
| | OF ?95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH |
| | AS REQUIRED |
| | BY THE AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED |
| | FROM THE COVERAGE AREA. |
| | |
| | RADIO COVERAGE IS REQUIRED WITH POSSIBLE DAS. PLEASE |
| | REVIEW TO SEE IF THE REQUIRED SYSTEM PERTAINS TO THE |
| | INTENT OF THAT COMMENT. |
| | |
| | THIS WORK SHALL BE UNDER SEPARATE SHOP DRAWINGS. |
| | |
| | |
| | |
| | 3) G 101 - THERE IS AN INDICATION OF A STAIR EGRESS |
| | FACTOR OF .2. |
| | |
| | PER NFPA 101, CH 7 , TABLE 7.3.3.1, THE STAIRWAY |
| | CAPCAITY FACTOR IS .3 |
| | |
| | PLEASE REVIEW AND MAKE THE APPLICABLE REVISIONS TO THE |
| | OCCUPANCY CALCULATIONS. |
| | |
| | |
| | |
| | |
| | 4) SHEET G111 - THERE IS AN INDICATION OF A CALCULATION |
| | FIGURE AT THE STAIRWELL EXIT DOOR OF [email protected] |
| | |
| | PER NFPA 101, CH 7 TABLE 7.3.3.1, THE LEVEL COMPENENTS |
| | OF THE EXIT IS .2 |
| | |
| | PLEASE REVIEW AND MAKE THE APPLICABLE REVISIONS TO THE |
| | OCCUPANCY CALCULATIONS. |
| | |
| | |
| | |
| | |
| | 5) SHEET G 111 & 113 - THERE IS AN INDICATION OF TRAVEL |
| | DISTANCE THAT APPEAR OVER 200' FROM THE SUITE DOOR TO |
| | THE EXIT. SOME REMOTE SUITES DO NOT SHOW THE TRAVEL |
| | DISTANCE. |
| | |
| | ADDITIONALLY, THERE IS AN INDICATION THAT THE CENTER |
| | STARIWAY IS NOT AN EXIT. |
| | |
| | PER NFPA 101, CH 28 |
| | |
| | 28.2.6.3.3 TRAVEL DISTANCE FROM THE CORRIDOR DOOR OF |
| | ANY GUEST |
| | ROOM OR GUEST SUITE TO THE NEAREST EXIT SHALL COMPLY |
| | WITH |
| | 28.2.6.3.3.1 AND 28.2.6.3.3.2. |
| | 28.2.6.3.3.1 TRAVEL DISTANCE FROM THE CORRIDOR DOOR OF |
| | ANY GUEST |
| | ROOM OR GUEST SUITE TO THE NEAREST EXIT SHALL BE |
| | MEASURED IN |
| | ACCORDANCE WITH SECTION 7.6 AND SHALL NOT EXCEED 200 FT |
| | (61 M) |
| | WHERE THE EXIT ACCESS AND ANY PORTION OF THE BUILDING |
| | THAT IS |
| | TRIBUTARY TO THE EXIT ACCESS ARE PROTECTED THROUGHOUT |
| | BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 28.3.5. |
| | |
| | PLEASE REVIEW AND CORRECT OR FURTHER CLARIFY/IDENTIFY |
| | TRAVLE DISTANCES PER NFPA 101. |
| | |
| | |
| | |
| | 6) SHEET A 441 - THERE ARE INDICATIONS THE STAIRWAY |
| | WIDTH IS 3'10" (46"). SHEETS G111 - G113 INDICATE THE |
| | STAIRWAY OCCUPANCY AT THE 34" DOOR AS 224. |
| | |
| | THE OCCUPANCY CAPACITY IS THE MOST RESTRICTIVE OF THE |
| | CAPACITY CALCULATIONS; 46' X .3 (PER NFPA 101 AS NOTED |
| | ABOVE) = 153 |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FFPC |
| | REFERENCES AND NAARRATIVE. |
| | |
| | |
| | |
| | 7) SHEET FP 002 - UNDER SECTION 1, A. 1) , THERE IS AN |
| | INDICATION OF AN INCORRECT (2010) REFERENCE TO THE |
| | CURRENT EDITION OF THE FFPC, 6TH EDITION, WHICH |
| | INCLUDES NFPA 1 AND 101, 2015. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 8) SHEET FP 002 - THERE IS AN INDICATION UNDER PART 3, |
| | 1, F, STANDPIPE TO BE TESTED AT 300 PSI FOR 1 HOUR. |
| | |
| | PER NFPA 14: |
| | |
| | 11.4 HYDROSTATIC TESTS. |
| | 11.4.1* GENERAL. ALL NEW SYSTEMS, INCLUDING YARD PIPING |
| | AND |
| | FIRE DEPARTMENT CONNECTIONS, SHALL BE TESTED |
| | HYDROSTATICALLY AT |
| | NOT LESS THAN 200 PSI (13.8 BAR) OF PRESSURE FOR 2 |
| | HOURS, OR AT |
| | 50 PSI (3.5 BAR) IN EXCESS OF THE MAXIMUM PRESSURE |
| | WHERE THE |
| | MAXIMUM PRESSURE IS IN EXCESS OF 150 PSI (10.3 BAR). |
| | 11.4.2 THE HYDROSTATIC TEST PRESSURE SHALL BE MEASURED |
| | AT THE |
| | LOW ELEVATION POINT OF THE INDIVIDUAL SYSTEM OR ZONE |
| | BEING TESTED. |
| | 11.4.3 THE STANDPIPE SYSTEM PIPING SHALL SHOW NO |
| | LEAKAGE |
| | OTHER THAN AS PERMITTED BY NFPA24, STANDARD FOR THE |
| | INSTALLATION |
| | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 8) SHEET FP 002 - PLEASE REVIEW ALL SPECIFIC CALL-OUTS |
| | WITHIN THE SHEET TO ENSURE THEY DO NOT CONFLICT WITH |
| | CURRENT CODE REQUIREMENTS AS THEY ARE TOO NUMEROUS FOR |
| | THIS REVIEW. |
| | |
| | FIRE INSPECTIONS WILL REVIEW COMPLIANCE WITH CURRENT |
| | CODE AND ANY REFERENCE WITHIN THE CURRENT CODE WILL BE |
| | ENFORCED WHEN MORE STRINGANT. |
| | |
| | |
| | |
| | 9) SHEET C 41 - THERE IS AN INDCIATION OF THE DDCV |
| | WITHIN THE HEIGHT OF THE BUILDING. |
| | |
| | PER NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE |
| | FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2013 |
| | EDITION |
| | |
| | 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS |
| | FOR FIRE |
| | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| | ONE |
| | OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| | (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FT (12 M) |
| | FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR |
| | VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH |
| | SECTION 6.4 |
| | (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT |
| | LESS THAN 40 FT (12 M) FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | BACKFLOW |
| | PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL |
| | BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5)*A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE |
| | VALVE |
| | WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, |
| | LOCATED NOT LESS THAN 40 FT (12 M) FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | NONINDICATING |
| | VALVE, SUCH AS AN UNDERGROUND GATE VALVE WITH AN |
| | APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, SHALL |
| | BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| | BUT |
| | AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF THE |
| | WALL |
| | FACING THE BACKFLOW PREVENTER. |
| | (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE |
| | FROM THE EXTERIOR |
| | (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE |
| | FROM THE EXTERIOR AS PERMITTED BY THE AUTHORITY HAVING |
| | JURISDICTION |
| | |
| | PLEASE REVIEW AND COMPLY WITH ONE OF THE APPLICABLE |
| | REQUIREMENT. |
| | |
| | |
| | |
| | 10) SHEET FP 404 - THERE IS AN INDICATION OF AN |
| | ELECTRIC FIRE PUMP, WHAT IS THE SECONDARY POWER SUPPLY? |
| | |
| | PER NFPA 20 |
| | |
| | 9.3 ALTERNATE POWER. |
| | 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT |
| | LEAST |
| | ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE |
| | THE |
| | HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY |
| | OF THE |
| | FIRE DEPARTMENT APPARATUS. |
| | 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT |
| | DESCRIBED IN |
| | 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE |
| | PROVIDED |
| | WHERE THE NORMAL SOURCE IS NOT RELIABLE. |
| | 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE |
| | PUMP |
| | SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE |
| | PUMP, |
| | BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP |
| | ELECTRIC |
| | MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE |
| | MEETING |
| | 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS STANDARD. |
| | 9.3.4 WHERE PROVIDED, THE ALTERNATE SOURCE OF POWER |
| | SHALL BE |
| | SUPPLIED FROM ONE OF THE FOLLOWING SOURCES: |
| | (1) A GENERATOR INSTALLED IN ACCORDANCE WITH SECTION |
| | 9.6 |
| | (2) ONE OF THE SOURCES IDENTIFIED IN 9.2.2(1), |
| | 9.2.2(2), 9.2.2(3), |
| | OR 9.2.2(5) WHERE THE POWER IS PROVIDED INDEPENDENT OF |
| | THE |
| | NORMAL SOURCE OF POWER |
| | 9.3.5 WHERE PROVIDED, THE ALTERNATE SUPPLY SHALL BE |
| | ARRANGED |
| | SO THAT THE POWER TO THE FIRE PUMP IS NOT DISRUPTED |
| | WHEN OVERHEAD |
| | LINES ARE DE-ENERGIZED FOR FIRE DEPARTMENT OPERATIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENT. |
| | |
| | |
| | |
| | |
| | 11) SHEET G111, A111B, & 005 - ON G111 THERE IS A |
| | INDICATION, AT THE REAR OF THE EMERGENCY ELECTRIC ROOM, |
| | OF A A 2 HR WALL TYPE, ON SHEET A111B THERE IS WALL |
| | CALL-OUT, C17, AT THE SAME LOCATION. |
| | |
| | SHEET A005, UNDER THE PARTITION SCHEDULE, C17 THERE IS |
| | NO FIRE RATING INDICATED. |
| | |
| | ADDITIONALLY, PER NFPA 110, STANDARD FOR EMERGENCY AND |
| | STANDBY POWER SYSTEMS, 2013 EDITION |
| | |
| | |
| | 7.2 LOCATION. |
| | 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE |
| | INSTALLED IN A |
| | SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS. |
| | 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST |
| | OF THE |
| | BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 12) SHEET E 111 B - AN ELECTRIC EMERGENCY GENERATOR IS |
| | INDICATED. |
| | |
| | THE EMERGENCY GENERATOR SHALL BE INSTALLED UNDER |
| | SEPARATE SHOP DRAWINGS AND COMPLY WITH THE REQUIRMENTS |
| | OF NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER |
| | SYSTEMS, 2013 EDITION. |
| | |
| | PLEASE PROVIDE A NOTE FOR THE PROPER LEVEL AND |
| | CLASSIFICATION, THE ALTERNATE FUEL SOURCE AND FUTURE |
| | SUBMITTAL OF SHOP DRAWINGS. |
| | |
| | |
| | |
| | |
| | 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE AS WELL AS IN ADDITION TO |
| | FUTHER REVIEW. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |